GEK-113032A
W650 Wind Generator Protection System
E-13
APPENDIX E
E.1 FACTORY DEFAULT SETTINGS
E
SETPOINT > PROTECTION ELEMENTS > POWER > DIRECTIONAL POWER>
DIRECTIONAL POWER 1> DIRECTIONAL POWER 2 > DIRECTIONAL POWER 3 > DIRECTIONAL POWER 4
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Block from off-line
Blk Time After Close
0.00
0.01 s
[0.00 : 900.00]
Directional Angle for stage 1
Dir Power Angle 1
0.00
1 Deg
[0.00 : 359.99]
Pickup level for stage 1
Stage 1 Tap
10.00
0.01MW
[-10000.00 : 10000.00]
Trip time for stage 1
Stage 1 Time
60.00
0.01 s
[0.00 : 900.00]
Directional Angle for stage 2
Dir Power Angle 2
0.00
1 Deg
[0.00 : 359.99]
Pickup level for stage 2
Stage 2 Tap
20.00
0.01MW
[-10000.00 : 10000.00]
Trip time for stage 2
Stage 2 Time
60.00
0.01 s
[0.00 : 900.00]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > PROTECTION ELEMENTS > VOLTAGE ELEMENTS >VOLTAGE UNBALANCE
VOLTAGE UNBALANCE 1 > VOLTAGE UNBALANCE 2 > VOLTAGE UNBALANCE 3>
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Pickup Level
Pickup Level
1
1 %
[3 : 500]
Trip Delay
Trip Delay
10.00
N/A
[DEFINITE TIME –
INVERSE TIME]
Reset Delay
Reset Delay
0.00
[0.00 : 900.00]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > SETTING GROUP
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Setting Grouping Permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Active Group
Active Group
GROUP 1
N/A
[GROUP 1 – GROUP 2 –
GROUP 3 – GROUP 4]
Snapshot Event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
SETPOINT > CONTROL ELEMENTS > UNDERFREQUENCY
UNDERFREQUENCY 1 > UNDERFREQUENCY 2 > UNDERFREQUENCY 3 > UNDERFREQUENCY 4
SETTING DESCRIPTION
NAME
DEFAULT VALUE
STEP
RANGE
USER
VALUE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Pickup level
Pickup Level
49.50
0.01 Hz
[20.00 : 65.00]
Trip time
Trip Delay
0.00
0.01 s
[0.00 : 900.00]
Reset time
Reset Delay
0.00
0.01 s
[0.00 : 900.00]
Minimum voltage threshold
Minimum Voltage
50
1 V
[30 : 500]
Snapshot event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
Содержание Multilin W650
Страница 2: ......
Страница 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Страница 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Страница 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Страница 360: ...7 48 W650 Wind Generator Protection System GEK 113032A 7 2 IEC 61850 PROFILE FOR W650 7 IEC 61850 PROTOCOL 7 ...
Страница 368: ...8 8 W650 Wind Generator Protection System GEK 113032A 8 4 OBJECT DICTIONARY 8 W650 CANOPEN PROFILE 8 ...
Страница 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Страница 422: ...13 6 W650 Wind Generator Protection System GEK 113032A 13 4 RELAY CONFIGURATION 13 FREQUENTLY ASKED QUESTIONS 13 ...
Страница 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 596: ...D 8 W650 Wind Generator Protection System GEK 113032A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...