5-68
W650 Wind Generator Protection System
GEK-113032A
5.4 PROTECTION ELEMENTS
5 SETTINGS
5
5.4.9 POWER
5.4.9.1 DIRECTIONAL POWER ELEMENT (32)
a) ELEMENT DESCRIPTION
The Directional Power element responds to three-phase active power measured from the feeder associated to the W650.
This element can be selected to operate according to the power threshold adjusted in the corresponding setting. This
element is ideal for reverse power applications (F32 REV) or forward power (F32 FWD), depending on the selected
setting. The relay measures the three-phase power for wye or delta connections.
The element has an adjustable characteristic angle and minimum operating power as shown in the Directional Power
Characteristic diagram. The element responds to the following condition:
P cos(
ϕ
) + Q sin (
ϕ
) > SMIN
where: P and Q are active and reactive powers as measured per the W650 convention,
ϕ
is the angle set at the 32 setting
(DIR POWER ANGLE) in degrees in steps of 0.01º, and SMIN is the minimum operating power.
The element has two independent (as to the pickup and delay settings) elements. Both elements can be used for alarm
and trip, and they can be set separately to provide a mixed power protection.
The Directional Power Characteristic is shown in the following diagram.
Figure 5–14: POWER DIRECTIONAL CHARACTERISTIC
By making the characteristic angle adjustable from 0º to 360º in steps of 0.01º, a variety of operating characteristics can be
achieved as presented in the figures below. For example, for an angle of 0º, the element would operate as a 32 Forward
Power element, while if setting an RCA angle of 180º, the element would operate as a 32 Reverse Power element. For
angles of 90º and 270º, the case would be similar but with reactive power.
DIR POWER ANGLE
Содержание Multilin W650
Страница 2: ......
Страница 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Страница 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Страница 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Страница 360: ...7 48 W650 Wind Generator Protection System GEK 113032A 7 2 IEC 61850 PROFILE FOR W650 7 IEC 61850 PROTOCOL 7 ...
Страница 368: ...8 8 W650 Wind Generator Protection System GEK 113032A 8 4 OBJECT DICTIONARY 8 W650 CANOPEN PROFILE 8 ...
Страница 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Страница 422: ...13 6 W650 Wind Generator Protection System GEK 113032A 13 4 RELAY CONFIGURATION 13 FREQUENTLY ASKED QUESTIONS 13 ...
Страница 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 596: ...D 8 W650 Wind Generator Protection System GEK 113032A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...