GEK-113032A
W650 Wind Generator Protection System
5-11
5 SETTINGS
5.2 PRODUCT SETUP
5
5.2.4.3 OSCILLOGRAPHY STATES
States associated to the oscillography module (“
Actual >Status>Records Status>Oscillography
”), are shown in Table 5–
13:
Table 5–13: OSCILLOGRAPHY STATES
OSC DIGITAL CHANNEL XX:
These states are configured at “
Setpoint>Relay configuration>Oscillography
”.
Each of these states can be associated to a protection state or to a virtual output. Each
oscillography record will reflect the changes experienced by this state during the
record.
OSCILLO TRIGGER:
The activation of this state will produce the oscillography record capture. Each record
uses a percentage of its capacity to store prefault information. This percentage is
selected in the Trigger Position setting, and the rest of the record’s capacity will store
post-fault information.
NUMBER OF TRIGGERS:
This is the number of the most recent oscillography record stored in the relay. The
record is stored in COMTRADE format. The range is 0 to 999.
CYCLES PER RECORD:
This state displays the number of cycles that will be stored in each oscillography
record. Although the number of cycles can be a decimal number, the record will
represent only the integer part.
AVAILABLE RECORDS:
This shows the number of records stored in the relay, which can be retrieved by serial
communication (ModBus RTU) or Ethernet (ftp, tftp). The range is 0 to 20.
OSCILLOGRAPHY STATES
OSC DIG CHANNEL 1
OSC DIG CHANNEL 2
OSC DIG CHANNEL 3
OSC DIG CHANNEL 4
OSC DIG CHANNEL 5
OSC DIG CHANNEL 6
OSC DIG CHANNEL 7
OSC DIG CHANNEL 8
OSC DIG CHANNEL 9
OSC DIG CHANNEL 10
OSC DIG CHANNEL 11
OSC DIG CHANNEL 12
OSC DIG CHANNEL 13
OSC DIG CHANNEL 14
OSC DIG CHANNEL 15
OSC DIG CHANNEL 16
OSCILLO TRIGGER
NUMBER OF TRIGGERS
CYCLES PER RECORD
AVAILABLE RECORDS
Содержание Multilin W650
Страница 2: ......
Страница 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Страница 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Страница 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Страница 360: ...7 48 W650 Wind Generator Protection System GEK 113032A 7 2 IEC 61850 PROFILE FOR W650 7 IEC 61850 PROTOCOL 7 ...
Страница 368: ...8 8 W650 Wind Generator Protection System GEK 113032A 8 4 OBJECT DICTIONARY 8 W650 CANOPEN PROFILE 8 ...
Страница 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Страница 422: ...13 6 W650 Wind Generator Protection System GEK 113032A 13 4 RELAY CONFIGURATION 13 FREQUENTLY ASKED QUESTIONS 13 ...
Страница 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 596: ...D 8 W650 Wind Generator Protection System GEK 113032A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...