GEK-113032A
W650 Wind Generator Protection System
3-9
3 HARDWARE
3.4 WIRING
3
3.4WIRING
3.4.1 EXTERNAL CONNECTIONS
W650 units can hold different options for F module:
Option 1:
Board with 16 digital inputs and 8 outputs.
Option 2:
Board with 8 digital inputs, 4 circuit supervision inputs, 6 conventional outputs, and two current sensing
outputs
Option 4:
Board with 32 digital inputs.
Option 5:
Board with 16 digital inputs and 8 analog inputs.
For slot G there are four different options:
Option 0:
No
board
Option 1:
Board with 16 digital inputs and 8 outputs.
Option 4:
Board with 32 digital inputs.
Option 5:
Board with 16 digital inputs and 8 analog inputs.
The number selected for slot G must be equal or higher than the number selected for option F for models including boards
4 and 5.
3.4.2 DIGITAL INPUTS WITH TRIP CIRCUIT SUPERVISION
The Option 2 I/O board includes two groups of 4 inputs with one common, in terminals F9 to F10. It also includes 6 auxiliary
outputs, in terminals F19 to F30 with normally open contacts and two current sensing (latching) outputs (F31-F33 and F34-
F36).
Besides, there are 2 groups of inputs for trip circuit supervision. The first group includes two isolated digital inputs, terminals
F1-F2 and F3-F4. The second group, symmetrical and identical to the first, is formed by isolated voltage inputs F15-F16
and F17-F18.
Using voltage detectors and current sensing, it is possible to implement several trip or close circuit supervision schemes, as
well as protection of the unit output contact.
In order to implement these schemes, it is not necessary to perform any setting in the unit. Internal functions are
always operative. The detailed description of trip circuit supervision is included in chapter 5 in this manual.
3.4.3 CABLE/FIBER ETHERNET BOARD
The Ethernet board is the communication board 2 (COM3) shown in Figure 3–2:. It is located in the bottom at the rear part
of the relay.
In Models C and D, the 10/100BaseTX port is selected by an internal switch. To select between fiber and cable it is
necessary to extract the board, switch the jumper to the selected position, as indicated on Figure 3–10: FIBER/CABLE
SELECTION and insert the board again. As with any other relay manipulation, the relay power supply must be removed
and the operation must be performed only by skilled personnel.
Содержание Multilin W650
Страница 2: ......
Страница 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Страница 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Страница 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Страница 360: ...7 48 W650 Wind Generator Protection System GEK 113032A 7 2 IEC 61850 PROFILE FOR W650 7 IEC 61850 PROTOCOL 7 ...
Страница 368: ...8 8 W650 Wind Generator Protection System GEK 113032A 8 4 OBJECT DICTIONARY 8 W650 CANOPEN PROFILE 8 ...
Страница 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Страница 422: ...13 6 W650 Wind Generator Protection System GEK 113032A 13 4 RELAY CONFIGURATION 13 FREQUENTLY ASKED QUESTIONS 13 ...
Страница 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 596: ...D 8 W650 Wind Generator Protection System GEK 113032A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...