GEK-113032A
W650 Wind Generator Protection System
C-3
APPENDIX C
C.1 DNP 3.0 PROTOCOL SETTINGS
C
38.
Msg Fragment Size
: This setting determines the size, in bytes, at which message fragmentation occurs. Large
fragment sizes allow for more efficient throughput; smaller fragment sizes cause more application layer
confirmations to be necessary which can provide for more robust data transfer over noisy communication channels
39-48. Binary Input Block x
: These settings allow customization and change of the size of DNP Binary Inputs point list.
The default Binary Inputs point list contains 160 points representing binary states that are configured using
“
Setpoint->Relay Configuration
” menu from the EnerVista 650 Setup program. These 160 binary states are
grouped in 10 blocks of 16 points each. There are 128 bits (8 blocks of 16) called
Control Events
and 32 bits (2
blocks of 16) corresponding to the states of 16
switchgears
available in W650 relay. If not all of the 160 points are
required in the DNP master, a custom Binary Inputs point list can be created by selecting up to 10 blocks of 16
points. Each block represents 16 Binary Input points. Block 1 represents Binary Input points 0-15, block 2
represents Binary Input points 16- 31, block 3 represents Binary Input points 32-47, etc. The minimum number of
Binary Input points that can be selected is 16 (1 block). If all of the
Binary Input Block x
settings are set to “NOT
USED”, the default list of 160 points will be in effect. The W650 will form the Binary Inputs points list from the
Binary Input Block x
settings up to the first occurrence of a setting value “NOT USED”. Permitted values for these
settings are: NOT USED, CTL EVENTS 1-16, CTL EVENTS 17-32, CTL EVENTS 33-48, CTL EVENTS 49-64, CTL
EVENTS 65-80, CTL EVENTS 81-96, CTL EVENTS 97-112, CTL EVENTS 113-128, SWITCHGEAR 1-8,
SWITCHGEAR 9-16.
Содержание Multilin W650
Страница 2: ......
Страница 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Страница 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Страница 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Страница 360: ...7 48 W650 Wind Generator Protection System GEK 113032A 7 2 IEC 61850 PROFILE FOR W650 7 IEC 61850 PROTOCOL 7 ...
Страница 368: ...8 8 W650 Wind Generator Protection System GEK 113032A 8 4 OBJECT DICTIONARY 8 W650 CANOPEN PROFILE 8 ...
Страница 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Страница 422: ...13 6 W650 Wind Generator Protection System GEK 113032A 13 4 RELAY CONFIGURATION 13 FREQUENTLY ASKED QUESTIONS 13 ...
Страница 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 596: ...D 8 W650 Wind Generator Protection System GEK 113032A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...