6-10
W650 Wind Generator Protection System
GEK-113032A
6.2 STATUS
6 ACTUAL VALUES
6
The AUTORECLOSE INTERNAL STATUS are internal signals provided by the autoreclose unit:
AR CLOSE BREAKER:
Breaker close command given by the autoreclose
AR OUT OF SERVICE:
Autoreclose out of service (Disabled)
AR READY:
Autoreclose in service
AR LOCKOUT:
Autoreclose in lockout status (finished cycled-definite trip)
AR BLOCK:
Autoreclose blocked (by input, logic, others, etc).
AR RCL IN PROGRESS:
Cycle in course (autoreclose in progress).
AR LCK BY ANOMALY:
Autoreclose in “Lockout” by anomaly.
AR LCK BY FAIL OPEN:
Autoreclose in “Lockout” by a failure in opening the breaker.
AR LCK BY FAIL CLOSE: Autoreclose in “Lockout” by a failure in closing the breaker.
AR LCK BY USER:
Autoreclose in “Lockout” by manual close.
AR LCK BY CONDS:
Autoreclose in “Lockout” by conditions. See input conditions configuration.
AR LCK BY TRIPS:
Autoreclose in “Lockout” by maximum number of trips.
AR LCK BY SHOTS:
Autoreclose in “Lockout” at the end of cycle – Definite trip.
AR BLK AFTER 1 SHOT:
Signal sent by the autoreclose after the 1
st
shot.
AR BLK AFTER 2 SHOT:
Signal sent by the autoreclose after the 2
nd
shot.
AR BLK AFTER 3 SHOT:
Signal sent by the autoreclose after the 3
rd
shot.
AR BLK AFTER 4 SHOT:
Signal sent by the autoreclose after the 4
th
shot.
AR BLOCK BY LEVEL:
Autoreclose blocked by level. See AR block signals configuration
AR BLOCK BY PULSE:
Autoreclose blocked by pulse. See AR block signals configuration
AR STATUS:
Autoreclose status (in service – out of service)
AR LOCKOUT MODE:
Relay “Lockout” status.
AR BLOCK MODE:
Relay “Block” status
Содержание Multilin W650
Страница 2: ......
Страница 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Страница 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Страница 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Страница 360: ...7 48 W650 Wind Generator Protection System GEK 113032A 7 2 IEC 61850 PROFILE FOR W650 7 IEC 61850 PROTOCOL 7 ...
Страница 368: ...8 8 W650 Wind Generator Protection System GEK 113032A 8 4 OBJECT DICTIONARY 8 W650 CANOPEN PROFILE 8 ...
Страница 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Страница 422: ...13 6 W650 Wind Generator Protection System GEK 113032A 13 4 RELAY CONFIGURATION 13 FREQUENTLY ASKED QUESTIONS 13 ...
Страница 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 596: ...D 8 W650 Wind Generator Protection System GEK 113032A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...