GEK-113032A
W650 Wind Generator Protection System
5-21
5 SETTINGS
5.3 SYSTEM SETUP
5
Table 5–22: FLEX CURVE SETTINGS
The definition of the curve points can be introduced directly in the Flex Curve settings menu. Alternatively they can be
created using the graphical tool provided by pressing
“Edit Curve”
in the Flex curves menu in EnerVista 650 Setup.
In the user curve edit screen (see Figure 5–2:), a base curve can be selected, from the Standard Curves menu. This curve
will be used as a template to create the user curve. Once the standard curve is viewed, it is possible to make the user curve
(operate, reset or both) reconcile the standard curve, using the
Flex curve > set flex curve from the standard curve
, and
then modifying any of the points by editing in the table the corresponding value.
The user can also view a different curve model to the one the FlexCurve has been adapted to, and compare both models to
adopt the most appropriate values in each case. If once the user curve has been configured the user wants to store the
information, the “
Flex Curve > Exit with Data
” menu must be selected. If the results are not to be saved, the
Exit without
Data
option must be selected. Now, calculated points must be saved in the Flex Curve using the "Store" option.
Figure 5–2: FLEXCURVES EDITION
SETPOINT > SYSTEM SETUP > FLEX CURVES
FLEX CURVES A > FLEX CURVES B> FLEX CURVES C > FLEX CURVES D
setting Description
Name
Default Value
Step
Range
Values for reset points 0.00 pkp
Time 0.00xPKP [RST]
0.000
0.001 s
[0.000 : 65.535]
Values for reset points 0.05 pkp
Time 0.05xPKP [RST]
0.000
0.001 s
[0.000 : 65.535]
…
…
…
…
…
Values for reset points 0.97 pkp
Time 0.97xPKP [RST]
0.000
0.001 s
[0.000 : 65.535]
Values for reset points 0.98 pkp
Time 0.98xPKP [RST]
0.000
0.001 s
[0.000 : 65.535]
Values for operation points 1.03 pkp
Time 1.03xPKP [OP]
0.000
0.001 s
[0.000 : 65.535]
Values for operation points 1.05 pkp
Time 1.05xPKP [OP]
0.000
0.001 s
[0.000 : 65.535]
…
…
…
…
…
Values for operation points 19.50 pkp
Time 19.50xPKP [OP]
0.000
0.001 s
[0.000 : 65.535]
Values for operation points 20.00 pkp
Time 20.00xPKP [OP]
0.000
0.001 s
[0.000 : 65.535]
Содержание Multilin W650
Страница 2: ......
Страница 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Страница 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Страница 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Страница 360: ...7 48 W650 Wind Generator Protection System GEK 113032A 7 2 IEC 61850 PROFILE FOR W650 7 IEC 61850 PROTOCOL 7 ...
Страница 368: ...8 8 W650 Wind Generator Protection System GEK 113032A 8 4 OBJECT DICTIONARY 8 W650 CANOPEN PROFILE 8 ...
Страница 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Страница 422: ...13 6 W650 Wind Generator Protection System GEK 113032A 13 4 RELAY CONFIGURATION 13 FREQUENTLY ASKED QUESTIONS 13 ...
Страница 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 596: ...D 8 W650 Wind Generator Protection System GEK 113032A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...