GEK-113032A
W650 Wind Generator Protection System
5-81
5 SETTINGS
5.5 CONTROL ELEMENTS
5
Once the breaker is open, it waits for the time set in the
Dead Time N
setting,
N
being the number of the cycle in
progress. If during this waiting the breaker is closed or reclose initiation conditions are given, the recloser will go to
LOCKOUT status by anomaly (AR LCK BY ANOMALY).
Once the Dead Time has expired, in case the
Conditions Permission
setting is disabled, a closing command would
be produced. If the conditions permission setting is enabled, the system will wait for the conditions fixed in the
conditions input (AR CONDS INPUT) configured at
Setpoint > Relay Configuration > Protection Elements
; if the
waiting period for the reclosing conditions signal activation exceeds the
Hold Time
, the autoreclose will go to Lockout
status by conditions (AR LCK BY CONDS).
The autoreclose gives a Closing command and waits for the breaker to close. If the
Fail to Close Time
setting is
exceeded, the autoreclose will go to lockout by failure of closing (AR LCK BY FAIL CLOSE).
At this point, the diagram indicates that a reclosing cycle has been reached, and so the cycle counter is increased. In this
time, the period set in
Reset Time
starts to count. If during the set element reset time there is no autoreclose initiation, the
cycle counter will reset to its initial value (1), and the autoreclose will return to the standby status (READY). If during the
Reset Time
setting period, there is a new autoreclose initiation, the
Reclose In Progress
sequence will start again. If this
reclose is produced after the last configured cycle in the
Maximum Number of Shots
setting, the autorecloser will go to
Lockout by maximum number of shots (AR LCK BY SHOTS).
AR LOCKOUT
This is a safety status, scheme lockout blocks all phases of the reclosing cycle, preventing automatic reclosure.
From the out of service (AR DISABLE) and BLOCK statuses, the autoreclose will stay in LOCKOUT prior to going to
READY.
From the RECLOSE IN PROGRESS status, the recloser will go to LOCKOUT status if any of the anomalies described
above occur.
To go from the LOCKOUT status to READY it is necessary that the breaker is closed and stays closed for preset time in
Reclaim Time
setting.
AR BLOCK
The BLOCK status is similar to the LOCKOUT status, as it guarantees that if the autoreclose is in Block, no breaker
close command will be produced, but the difference between them is that this Block status is reached by an external
action. The autoreclose block can be configured by pulse or level signals. This configuration must be selected at
Setpoint > Relay Configuration > Protection Elements
When the autoreclose block signal is deactivated, either by a level change in the set signal (in case of block by level) or
by an Unblock pulse (in case of block by pulse), the block status is abandoned and the autoreclose returns to the
Lockout status.
Configurable signals to block the autorecloser are described in section 5.5.4.3.
Содержание Multilin W650
Страница 2: ......
Страница 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Страница 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Страница 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Страница 360: ...7 48 W650 Wind Generator Protection System GEK 113032A 7 2 IEC 61850 PROFILE FOR W650 7 IEC 61850 PROTOCOL 7 ...
Страница 368: ...8 8 W650 Wind Generator Protection System GEK 113032A 8 4 OBJECT DICTIONARY 8 W650 CANOPEN PROFILE 8 ...
Страница 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Страница 422: ...13 6 W650 Wind Generator Protection System GEK 113032A 13 4 RELAY CONFIGURATION 13 FREQUENTLY ASKED QUESTIONS 13 ...
Страница 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 596: ...D 8 W650 Wind Generator Protection System GEK 113032A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...