GEK-113032A
W650 Wind Generator Protection System
5-47
5 SETTINGS
5.4 PROTECTION ELEMENTS
5
The polarization diagram is as follows:
Figure 5–9: POLARIZATION DIAGRAM
The diagram shows a fault in phase A, therefore the Operation magnitude is IA, the polarization magnitude is VBC, which
has been rotated the torque angle set as
MTA
. Positive angles are considered as counter clockwise rotations, and negative
angles clockwise rotations. Direction is considered to be forward when the fault current is inside an arc of ±90º to both sides
of the polarization voltage. In the directional element settings there is a
Direction
setting that allows to select in which area
the element operation is allowed, either forward or reverse. Operation areas include a safety zone of 5º to each side of the
cone. This safety cone is applied when the operation direction calculation is performed from initial block conditions. When
we go from a non-trip area to a trip area, the safety cone is considered. In case we go from a trip area to a non-trip area,
this cone will not be considered, and the whole area will be operative. This safety cone is located always in the operation
area, both in forward and reverse cases.
NOTE
: In situations where a current inversion is produced during a fault, the phase directional element will require a period
of time to establish the blocking signal. This time is approximately 20 ms. Certain instantaneous overcurrent elements can
be activated before receiving the blocking signal from the directional element. In cases where these situations can be
expected, we recommend to add a 50ms delay to IOC elements.
Содержание Multilin W650
Страница 2: ......
Страница 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Страница 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Страница 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Страница 360: ...7 48 W650 Wind Generator Protection System GEK 113032A 7 2 IEC 61850 PROFILE FOR W650 7 IEC 61850 PROTOCOL 7 ...
Страница 368: ...8 8 W650 Wind Generator Protection System GEK 113032A 8 4 OBJECT DICTIONARY 8 W650 CANOPEN PROFILE 8 ...
Страница 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Страница 422: ...13 6 W650 Wind Generator Protection System GEK 113032A 13 4 RELAY CONFIGURATION 13 FREQUENTLY ASKED QUESTIONS 13 ...
Страница 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 596: ...D 8 W650 Wind Generator Protection System GEK 113032A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...