GEK-113032A
W650 Wind Generator Protection System
13-1
13 FREQUENTLY ASKED QUESTIONS
13.1 COMMUNICATIONS
13
13 FREQUENTLY ASKED QUESTIONS 13.1COMMUNICATIONS
Q1
Does the W650 support DNP and ModBus over the Ethernet port?
A1
W650 units support both protocols over both the asynchronous serial ports and the Ethernet LAN synchronous port
using TCP/IP and UDP/IP layers over the Ethernet.
Q2
Does this equipment support dual IP access?
A1
Yes, it supports two independent IP addresses in aliasing mode. Those address go in the communications settings
Network0 and Network1.
Q3
Is the protocol IEC 870-103 supported by the W650?
A3
At this moment it is not supported.
Q4
Can the W650 be used as a DNP master station?
A4
Not at this moment. It works as a slave IED station for all protocols.
Q5
How many communication ports are included in the W650?
A5
The equipment has 2 different boards, one for asynchronous serial ports and another for a high-speed synchronous
Ethernet port. The first board has 2 comm ports, COM1 and COM2. COM2 is multiplexed with the front serial RS232
port, whereas the COM1 port is completely independent from COM2.
The synchronous LAN port is COM3.
Q6
Are there one or two Ethernet ports?
A6
The equipment has only 1 Ethernet port. For redundant fiber optic versions, redundancy is done at the physical level
(fiber optic) but there is just one port.
Q7
How many different communication Ethernet sessions can be opened through the LAN port?
A7
ModBus TCP/IP:4 sockets
DNP TCP/IP:3 sessions
Q8
May I use the cooper 10/100 BaseTX connection included in the basic model with all protocols?
A8
Yes, it may be used with all protocols. In noisy substation environments and/or long distances, it is recommended to
use fiber optic options due to much better EMC performance and immunity. For fiber optic models, it is necessary to
adjust an internal jumper to use the copper port.
Q9
Remote I/O CAN bus. Does it support DeviceNet protocol?
A9
No it does not support DeviceNet.
Q10
Which functions are available in the relay web server?
A10
Currently, it includes several functions for viewing measures and retrieving information.
Q11
What is the web site user password and name?
A11
The password is: 7169 and user name is: GE
Содержание Multilin W650
Страница 2: ......
Страница 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Страница 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Страница 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Страница 360: ...7 48 W650 Wind Generator Protection System GEK 113032A 7 2 IEC 61850 PROFILE FOR W650 7 IEC 61850 PROTOCOL 7 ...
Страница 368: ...8 8 W650 Wind Generator Protection System GEK 113032A 8 4 OBJECT DICTIONARY 8 W650 CANOPEN PROFILE 8 ...
Страница 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Страница 422: ...13 6 W650 Wind Generator Protection System GEK 113032A 13 4 RELAY CONFIGURATION 13 FREQUENTLY ASKED QUESTIONS 13 ...
Страница 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 596: ...D 8 W650 Wind Generator Protection System GEK 113032A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...