B-78
W650 Wind Generator Protection System
GEK-113032A
B.7 MEMORY MAP
APPENDIX B
B
ADDRESS BIT
NAME
FORMAT STEP MODE LENGTH MISCELLANEOUS
Ajustes Unidad Direccional de Tierra Grupo 1 - Ground Directional 3
0x269F
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x26A0
MTA
F003
1
R/W
2
[-90 , 90] Deg
0x26A2
Direction
F012
1
R/W
1
0=REVERSE
1=FORWARD
0x26A3
Polarization
F012
1
R/W
1
0=VO
1=IP
2=VO + IP
3=VO*IP
0x26A4
Block
Logic
F012
1
R/W
1
0=PERMISSION
1=BLOCK
0x26A5
Pol V Threshold
F003
1
R/W
2
[0 , 500] V
0x26A7
Snapshot
Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x26BA
Confirmation
address
W
1
Ajustes Unidad Direccional de Tierra Grupo 2 - Ground Directional 2
0x26BB
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x26BC
MTA
F003
1
R/W
2
[-90 , 90] Deg
0x26BE
Direction
F012
1
R/W
1
0=REVERSE
1=FORWARD
0x26BF
Polarization
F012
1
R/W
1
0=VO
1=IP
2=VO + IP
3=VO*IP
0x26C0
Block
Logic
F012
1
R/W
1
0=PERMISSION
1=BLOCK
0x26C1
Pol V Threshold
F003
1
R/W
2
[0 , 500] V
0x26C3
Snapshot
Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x26D6
Confirmation
address
W
1
Ajustes Unidad Direccional de Tierra Grupo 3 - Ground Directional 3
0x26D7
Function
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x26D8
MTA
F003
1
R/W
2
[-90 , 90] Deg
0x26DA
Direction
F012
1
R/W
1
0=REVERSE
1=FORWARD
0x26DB
Polarization
F012
1
R/W
1
0=VO
1=IP
2=VO + IP
3=VO*IP
0x26DC
Block
Logic
F012
1
R/W
1
0=PERMISSION
1=BLOCK
0x26DD
Pol V Threshold
F003
1
R/W
2
[0 , 500] V
0x26DF
Snapshot
Events
F012
1
R/W
1
0=DISABLED
1=ENABLED
0x26F2
Confirmation
address
W
1
Содержание Multilin W650
Страница 2: ......
Страница 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Страница 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Страница 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Страница 360: ...7 48 W650 Wind Generator Protection System GEK 113032A 7 2 IEC 61850 PROFILE FOR W650 7 IEC 61850 PROTOCOL 7 ...
Страница 368: ...8 8 W650 Wind Generator Protection System GEK 113032A 8 4 OBJECT DICTIONARY 8 W650 CANOPEN PROFILE 8 ...
Страница 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Страница 422: ...13 6 W650 Wind Generator Protection System GEK 113032A 13 4 RELAY CONFIGURATION 13 FREQUENTLY ASKED QUESTIONS 13 ...
Страница 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 596: ...D 8 W650 Wind Generator Protection System GEK 113032A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...