5-4
W650 Wind Generator Protection System
GEK-113032A
5.2 PRODUCT SETUP
5 SETTINGS
5
5.2.1.4 DNP3 SLAVE
Physical port, Slave Address for DNP, IP Addresses for Masters, TCP/UDP Port, Unsolicited Response parameters, Analog
scale factors and deadbands, message fragment size, Binary input block. For more detailed information go to appendix C
in this manual.
Table 5–5: DNP PROTOCOL SETTINGS
PRODUCT SETUP>COMMUNICATION SETTINGS >DNP3 SLAVE
DNP3 SLAVE 1 > DNP3 SLAVE 2 > DNP3 SLAVE 3
Name
Default Value
Step
Range
Physical Port
NONE
N/A
[COM1:COM2:NETWORK]
Address
255
1
[0 : 65534]
IP Addr Client1 Oct1
0
1
[0 : 255]
IP Addr Client1 Oct2
0
1
[0 : 255]
IP Addr Client1 Oct3
0
1
[0 : 255]
IP Addr Client1 Oct4
0
1
[0 : 255]
IP Addr Client2 Oct1
0
1
[0 : 255]
IP Addr Client2 Oct2
0
1
[0 : 255]
IP Addr Client2 Oct3
0
1
[0 : 255]
IP Addr Client2 Oct4
0
1
[0 : 255]
IP Addr Client3 Oct1
0
1
[0 : 255]
IP Addr Client3 Oct2
0
1
[0 : 255]
IP Addr Client3 Oct3
0
1
[0 : 255]
IP Addr Client3 Oct4
0
1
[0 : 255]
IP Addr Client4 Oct1
0
1
[0 : 255]
IP Addr Client4 Oct2
0
1
[0 : 255]
IP Addr Client4 Oct3
0
1
[0 : 255]
IP Addr Client4 Oct4
0
1
[0 : 255]
IP Addr Client5 Oct1
0
1
[0 : 255]
IP Addr Client5 Oct2
0
1
[0 : 255]
IP Addr Client5 Oct3
0
1
[0 : 255]
IP Addr Client5 Oct4
0
1
[0 : 255]
TCP/UDP Port
20000
1
[0 : 65535]
Unsol Resp Function
DISABLED
N/A
[DISABLED – ENABLED]
Unsol Resp TimeOut
5
1
[0 : 60]
Unsol Resp Max Ret
10
1
[0 : 255]
Unsol Resp Dest Adr
200
1
[0 : 65535]
Current Scale Factor
1
N/A
[0.00001-0.0001-0.001-0.01-0.1-1-10-100-1000]
Voltage Scale Factor
1
N/A
[0.00001-0.0001-0.001-0.01-0.1-1-10-100-1000]
Power Scale Factor
1
N/A
[0.00001-0.0001-0.001-0.01-0.1-1-10-100-1000]
Energy Scale Factor
1
N/A
[0.00001-0.0001-0.001-0.01-0.1-1-10-100-1000]
Other Scale Factor
1
N/A
[0.00001-0.0001-0.001-0.01-0.1-1-10-100-1000]
Current Deadband
30000
1
[0 : 65535]
Voltage Deadband
30000
1
[0 : 65535]
Power Deadband
30000
1
[0 : 65535]
Energy Deadband
30000
1
[0 : 65535]
Other Deadband
30000
1
[0 : 65535]
Msg Fragment Size
240
1
[30 : 2048]
Binary Input Block 1
CTL EVENTS 1-16
N/A
Binary Input Block 2
CTL EVENTS 17-32
N/A
Binary Input Block 3
CTL EVENTS 33-48
N/A
Binary Input Block 4
CTL EVENTS 49-64
N/A
Binary Input Block 5
CTL EVENTS 65-80
N/A
Содержание Multilin W650
Страница 2: ......
Страница 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Страница 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Страница 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Страница 360: ...7 48 W650 Wind Generator Protection System GEK 113032A 7 2 IEC 61850 PROFILE FOR W650 7 IEC 61850 PROTOCOL 7 ...
Страница 368: ...8 8 W650 Wind Generator Protection System GEK 113032A 8 4 OBJECT DICTIONARY 8 W650 CANOPEN PROFILE 8 ...
Страница 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Страница 422: ...13 6 W650 Wind Generator Protection System GEK 113032A 13 4 RELAY CONFIGURATION 13 FREQUENTLY ASKED QUESTIONS 13 ...
Страница 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 596: ...D 8 W650 Wind Generator Protection System GEK 113032A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...