W650 Wind Generator Protection System
GEK-113032A
5.3 SYSTEM SETUP
5 SETTINGS
5
5.3SYSTEM SETUP
This section shows the settings related to the system setup definition.
5.3.1 GENERAL SETTINGS
This section determines the settings of the element configuration regarding its connection to the power system.
Access to these settings using the EnerVista 650 Setup software is at
Setpoint > System Setup > General settings.
The corresponding settings are shown on the table below:
Table 5–21: GENERAL SETTINGS
The system rated voltage is used as reference by the voltage restraint in the phase timed overcurrent element.
The Frequency reference marks the voltage channel to which the system Frequency is measured.
The auxiliary voltage setting can be selected between VN and VX.
VN means that all elements using neutral voltage will take the value directly from the fourth voltage input.
VX means that all elements using neutral voltage will take the value calculated from phase voltages.
5.3.2 FLEX CURVES
The relay incorporates 4 user curves called Flex Curve A, B, C and D. The points for these curves are defined by the user
in
“Setpoint>System Setup>Flex Curves”
menu in EnerVista 650 Setup. User defined flex curves can be selected as an
operation curve in all the time overcurrent functions in the relay.
In the flex curves menu there are 120 points to define a user curve. 40 points for reset (from 0 to 0.98 times the pickup
value) and 80 for operate (from 1.03 to 20 times the pickup).
SETPOINT > SYSTEM SETUP > GENERAL SETTINGS
setting Description
Name
Default Value
Step
Range
Phase CT ratio
Phase CT Ratio
1.0
0.1
[1.0 : 6000.0]
Ground CT ratio
Ground CT Ratio
1.0
0.1
[1.0 : 6000.0]
Sensitive ground CT ratio
Stv Ground CT Ratio
1.0
0.1
[1.0 : 6000.0]
Phase VT ratio
Phase VT Ratio
1.0
1.0
[1.0 : 1.500.0]
Phase VT connection
Phase VT Connection
WYE
N/A
[WYE – DELTA]
Rated voltage
Nominal Voltage
690.0
0.1
[1.0 : 850.0]
Rated Frequency
Nominal Frequency
50 Hz
1 Hz
[50-60]
Phase rotation
Phase Rotation
ABC
N/A
[ABC – ACB]
Frequency reference
Frequency Reference
VI
N/A
[VI-VII-VIII]
Auxiliary Voltage
Auxiliary Voltage
VX
N/A
[VX – VN]
Snapshot Event generation
Snapshot Events
DISABLED
N/A
[DISABLED – ENABLED]
Содержание Multilin W650
Страница 2: ......
Страница 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Страница 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Страница 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Страница 360: ...7 48 W650 Wind Generator Protection System GEK 113032A 7 2 IEC 61850 PROFILE FOR W650 7 IEC 61850 PROTOCOL 7 ...
Страница 368: ...8 8 W650 Wind Generator Protection System GEK 113032A 8 4 OBJECT DICTIONARY 8 W650 CANOPEN PROFILE 8 ...
Страница 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Страница 422: ...13 6 W650 Wind Generator Protection System GEK 113032A 13 4 RELAY CONFIGURATION 13 FREQUENTLY ASKED QUESTIONS 13 ...
Страница 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 596: ...D 8 W650 Wind Generator Protection System GEK 113032A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...