5-246
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
GROUPED ELEMENTS
CHAPTER 5: SETTINGS
5
The power swing detect element provides both power swing blocking and out-of-step tripping functions. The element
measures the positive-sequence apparent impedance and traces its locus with respect to either two or three user-
selectable operating characteristic boundaries. Upon detecting appropriate timing relations, the blocking and/or tripping
indications are given through FlexLogic operands. The element incorporates an adaptive disturbance detector. This
function does not trigger on power swings, but is capable of detecting faster disturbances—faults in particular—that can
occur during power swings. Operation of this dedicated disturbance detector is signaled via the
POWER SWING 50DD
operand.
The power swing detect element asserts two operands intended for blocking selected protection elements on power
swings:
POWER SWING BLOCK
is a traditional signal that is safely asserted for the entire duration of the power swing, and
POWER SWING UN/BLOCK
is established in the same way, but resets when an extra disturbance is detected during the power
swing. The
POWER SWING UN/BLOCK
operand can be used for blocking selected protection elements if the intent is to
respond to faults during power swing conditions.
Different protection elements respond differently to power swings. If tripping is required for faults during power swing
conditions, some elements can be blocked permanently (using the
POWER SWING BLOCK
operand), and others can be
blocked and dynamically unblocked upon fault detection (using the
POWER SWING UN/BLOCK
operand).
POWER SWING INNER
LIMIT ANGLE: 60°
Range: 40 to 140° in steps of 1
POWER SWING OUTER
RGT BLD: 100.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
POWER SWING OUTER
LFT BLD: 100.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
POWER SWING MIDDLE
RGT BLD: 100.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
POWER SWING MIDDLE
LFT BLD: 100.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
POWER SWING INNER
RGT BLD: 100.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
POWER SWING INNER
LFT BLD: 100.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
POWER SWING PICKUP
DELAY 1: 0.030 s
Range: 0.000 to 65.535 s in steps of 0.001
POWER SWING RESET
DELAY 1: 0.050 s
Range: 0.000 to 65.535 s in steps of 0.001
POWER SWING PICKUP
DELAY 2: 0.017 s
Range: 0.000 to 65.535 s in steps of 0.001
POWER SWING PICKUP
DELAY 3: 0.009 s
Range: 0.000 to 65.535 s in steps of 0.001
POWER SWING PICKUP
DELAY 4: 0.017 s
Range: 0.000 to 65.535 s in steps of 0.001
POWER SWING SEAL-IN
DELAY: 0.400 s
Range: 0.000 to 65.535 s in steps of 0.001
POWER SWING TRIP
MODE: Delayed
Range: Early, Delayed
POWER SWING BLK:
Off
Range: FlexLogic operand
POWER SWING
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
POWER SWING
EVENTS: Disabled
Range: Disabled, Enabled
Содержание L90
Страница 14: ...1 4 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 68: ...2 54 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 136: ...3 68 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 224: ...4 88 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 692: ...6 36 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 708: ...7 16 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 742: ...9 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 804: ...10 62 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 872: ...C 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 878: ...D 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 882: ...iv L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 900: ...xviii L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...