CHAPTER 5: SETTINGS
PRODUCT SETUP
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-131
5
PUSHBTN 1 ON TEXT
— This setting specifies the bottom 20-character line of the user-programmable pushbutton message
and is displayed when the pushbutton is in the “on” position. For example, the text displays in the Event Record. See the
User-definable Displays section for instructions on entering alphanumeric characters from the keypad. On a graphical
front panel, this setting instead controls the on status text of the user-programmable pushbutton component on single-
line diagrams. This setting is not applied to the physical pushbuttons on the graphical front panel.
PUSHBTN 1 OFF TEXT
— This setting specifies the bottom 20-character line of the user-programmable pushbutton message
and displays when the pushbutton is deactivated and the
PUSHBUTTON 1 FUNCTION
is “Latched.” A message does not
display when the
PUSHBUTTON 1 FUNCTION
is “Self-reset” as the pushbutton operand status is implied to be “Off” upon its
release. The length of the “Off” message is configured with the
PRODUCT SETUP
DISPLAY PROPERTIES
FLASH MESSAGE
TIME
setting. On a graphical front panel, this setting instead controls the off status text of the user-programmable
pushbutton component on single-line diagrams. This setting is not applied to the physical pushbuttons on the graphical
front panel.
PUSHBTN 1 HOLD
— This setting specifies the time required for a front panel pushbutton to be pressed before it is deemed
active. This timer is reset upon release of the pushbutton. Note that user-programmable pushbutton operation requires the
front panel pushbutton to be pressed a minimum of 50 ms. This minimum time is required prior to activating the user-
programmable pushbutton hold timer.
PUSHBTN 1 SET
— This setting assigns the FlexLogic operand serving to activate the user-programmable pushbutton
element. The duration of the incoming set signal must be at least 50 ms.
PUSHBTN 1 RESET
— This setting assigns the FlexLogic operand serving to deactivate the user-programmable pushbutton
element. This setting is applicable only if the user-programmable pushbutton is in "Latched" mode.
PUSHBTN 1 AUTORST
— This setting enables the user-programmable pushbutton autoreset feature. This setting is applicable
only if the pushbutton is in “Latched” mode.
PUSHBTN 1 AUTORST DELAY
— This setting specifies the time delay for automatic reset of the pushbutton when in "Latched"
mode.
PUSHBTN 1 REMOTE
— This setting assigns the FlexLogic operand serving to inhibit user-programmable pushbutton
operation from the operand assigned to the
PUSHBTN 1 SET
or
PUSHBTN 1 RESET
settings.
PUSHBTN 1 LOCAL
— This setting assigns the FlexLogic operand serving to inhibit user-programmable pushbutton operation
from the front panel pushbuttons. This inhibit functionality is not applicable to pushbutton autoreset.
PUSHBTN 1 DROP-OUT TIME
— This setting applies only to “Self-Reset” mode and specifies the duration of the user-
programmable pushbutton active status after the front panel pushbutton or graphical front panel interface pushbutton
has been released. When activated remotely, this setting specifies the entire activation time of the pushbutton; the length
of time the operand selected by
PUSHBTN 1 SET
remains on has no effect on the pulse duration.
PUSHBTN 1 LED CTL
— This setting assigns the FlexLogic operand serving to drive the front panel pushbutton LED. If this
setting is “Off,” then LED operation is directly linked to the
PUSHBUTTON 1 ON
operand. This setting is not applied to
pushbuttons 9 to 16 on the graphical front panel, where the label background shows the orange glow color for the "on"
state.
PUSHBTN 1 MESSAGE
— This setting controls the behavior of the user-programmable pushbutton on message that is
programmed in the
PUSHBTN 1 ID
and
PUSHBTN 1 ON TEXT
settings, and the behavior of the user-programmable pushbutton
off message that is programmed in the
PUSHBTN 1 ID
and
PUSHBTN 1 OFF TEXT
settings. This settings has no effect on the
graphical front panel.
When set to "Disabled", user-programmable pushbutton messages do not display. Otherwise the on message displays
when the user-programmable pushbutton becomes activated, and if in the "Latched" mode the off message displays when
the user-programmable pushbutton becomes deactivated.
When set to "Normal", the duration the message displays is as specified by the
FLASH MESSAGE TIME
setting.
When set to "High Priority", the duration of the off message is as specified by the
FLASH MESSAGE TIME
setting, but the on
message is displayed as long as the user-programmable pushbutton is activated. While activated, target and other
messages are suppressed. To allow front panel keypad operation, when a keypad button is pressed the message is
supressed for 10 seconds.
PUSHBUTTON 1 EVENTS
— If this setting is enabled, each user-programmable pushbutton state change is logged as an
event into the event recorder.
Содержание L90
Страница 14: ...1 4 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 68: ...2 54 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 136: ...3 68 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 224: ...4 88 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 692: ...6 36 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 708: ...7 16 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 742: ...9 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 804: ...10 62 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 872: ...C 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 878: ...D 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 882: ...iv L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 900: ...xviii L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...