CHAPTER 5: SETTINGS
CONTROL ELEMENTS
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-365
5
The CT failure function detects problems with system current transformers used to supply current to the relay. This logic
detects the presence of a zero-sequence current at the supervised source of current without a simultaneous zero-
sequence current at another source, zero-sequence voltage, or some protection element condition.
The CT failure logic (see later) is based on the presence of the zero-sequence current in the supervised CT source and the
absence of one of three or all of the three following conditions:
•
Zero-sequence current at different source current (can be different set of CTs or different CT core of the same CT)
•
Zero-sequence voltage at the assigned source
•
Appropriate protection element or remote signal
Settings are described as follows. There are four CT FAIL functions with the breaker and half software option and two
without.
CT FAIL 1 FUNCTION
— Enables or disables operation of the CT failure element.
CT FAIL 1 BLOCK
— Selects a FlexLogic operand to block operation of the element during some condition (for example, an
open pole in process of the single pole tripping-reclosing). Local signals or remote signals representing operation of some
remote current protection elements via communication channels can also be chosen.
CT FAIL 1 3I0 INPUT 1
— Selects the current source for input 1. The most critical protection element should also be assigned
to the same source.
CT FAIL 1 3I0 INPUT 1 PICKUP
— Selects the 3I_0 pickup value for input 1 (the main supervised CT source).
CT FAIL 1 3I0 INPUT 2
— Selects the current source for input 2. Input 2 should use a different set of CTs or a different CT core
of the same CT. If 3I_0 does not exist at source 2, then a CT failure is declared.
CT FAIL 1 3I0 INPUT 2 PICKUP
— Selects the 3I_0 pickup value for input 2 (different CT input) of the relay.
CT FAIL 1 3V0 INPUT
— Selects the voltage source.
CT FAIL 1 3V0 INPUT PICKUP
— Specifies the pickup value for the 3V_0 source.
CT FAIL 1 PICKUP DELAY
— Specifies the pickup delay of the CT failure element.
CT FAIL 1 PICKUP
DELAY: 1.000 s
Range: 0.000 to 65.535 s in steps of 0.001
CT FAIL 1 TARGET:
Self-reset
Range: Self-reset, Latched, Disabled
CT FAIL 1 EVENTS:
Disabled
Range: Disabled, Enabled
Содержание L90
Страница 14: ...1 4 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 68: ...2 54 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 136: ...3 68 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 224: ...4 88 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 692: ...6 36 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 708: ...7 16 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 742: ...9 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 804: ...10 62 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 872: ...C 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 878: ...D 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 882: ...iv L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 900: ...xviii L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...