CHAPTER 5: SETTINGS
CONTROL ELEMENTS
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-353
5
5.8.11.2 Breaker arcing current
SETTINGS
CONTROL ELEMENTS
MONITORING ELEMENTS
BREAKER 1(4) ARCING CURRENT
There is one breaker arcing current element available per CT bank, with a minimum of two elements. This element
calculates an estimate of the per-phase wear on the breaker contacts by measuring and integrating the current squared
passing through the breaker contacts as an arc. These per-phase values are added to accumulated totals for each phase
and compared to a programmed threshold value. When the threshold is exceeded in any phase, the relay can set an
output operand to “1.” The accumulated value for each phase can be displayed as an actual value.
The operation of the scheme is shown in the following logic diagram. The same output operand that is selected to operate
the output relay used to trip the breaker, indicating a tripping sequence has begun, is used to initiate this feature. A time
delay is introduced between initiation and the starting of integration to prevent integration of current flow through the
breaker before the contacts have parted. This interval includes the operating time of the output relay, any other auxiliary
CT FAILURE
DETECTOR 4
VT FUSE FAILURE 1
VT FUSE FAILURE 4
OPEN POLE
THERMAL OVERLOAD
PROTECTION
BROKEN CONDUCTOR
BREAKER 1
ARCING CURRENT
BKR 1 ARC AMP
FUNCTION: Disabled
Range: Disabled, Enabled
BKR 1 ARC AMP
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
BKR 1 ARC AMP INT-A:
Off
Range: FlexLogic operand
BKR 1 ARC AMP INT-C:
Off
Range: FlexLogic operand
BKR 1 ARC AMP
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
BKR 1 ARC AMP LIMIT:
1000 kA2-cyc
Range: 0 to 50000 kA
2
-cycle in steps of 1
BKR 1 INTERRUPTION
RATING: 31.5 kA
Range: 0.0 to 100.0 kA in steps of 0.1
BKR 1 CLR ARC AMPS:
Off
Range: FlexLogic operand
BKR 1 ARC AMP BLOCK:
Off
Range: FlexLogic operand
BKR 1 ARC AMP
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
BKR 1 ARC AMP
EVENTS: Disabled
Range: Disabled, Enabled
Содержание L90
Страница 14: ...1 4 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 68: ...2 54 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 136: ...3 68 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 224: ...4 88 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 692: ...6 36 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 708: ...7 16 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 742: ...9 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 804: ...10 62 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 872: ...C 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 878: ...D 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 882: ...iv L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 900: ...xviii L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...