5-424
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
TRANSDUCER INPUTS/OUTPUTS
CHAPTER 5: SETTINGS
5
Settings are automatically generated for every channel available in the specific relay as shown above for the first channel
of a type 5C transducer module installed in the first available slot.
The function of the channel can be either “Enabled” or “Disabled.” If “Disabled,” there is not an actual value created for the
channel. An alphanumeric ID is assigned to the channel; this ID is included in the channel actual values. It is also used to
reference the channel as the input parameter to features designed to measure this type of parameter. Selecting the type of
RTD connected to the channel configures the channel.
Actions based on RTD overtemperature, such as trips or alarms, are done in conjunction with the FlexElements feature. In
FlexElements, the operate level is scaled to a base of 100°C. For example, a trip level of 150°C is achieved by setting the
operate level at 1.5 pu. FlexElement operands are available to FlexLogic for further interlocking or to operate an output
contact directly.
See the following table for reference temperature values for each RTD type.
Table 5-44: RTD temperature vs. resistance
Temperature
Resistance (in ohms)
°C
°F
100
Ω
Pt
(DIN 43760)
120
Ω
Ni
100
Ω
Ni
10
Ω
Cu
–50
–58
80.31
86.17
71.81
7.10
–40
–40
84.27
92.76
77.30
7.49
–30
–22
88.22
99.41
82.84
7.88
–20
–4
92.16
106.15
88.45
8.26
–10
14
96.09
113.00
94.17
8.65
0
32
100.00
120.00
100.00
9.04
10
50
103.90
127.17
105.97
9.42
20
68
107.79
134.52
112.10
9.81
30
86
111.67
142.06
118.38
10.19
40
104
115.54
149.79
124.82
10.58
50
122
119.39
157.74
131.45
10.97
60
140
123.24
165.90
138.25
11.35
70
158
127.07
174.25
145.20
11.74
80
176
130.89
182.84
152.37
12.12
90
194
134.70
191.64
159.70
12.51
100
212
138.50
200.64
167.20
12.90
110
230
142.29
209.85
174.87
13.28
120
248
146.06
219.29
182.75
13.67
130
266
149.82
228.96
190.80
14.06
140
284
153.58
238.85
199.04
14.44
150
302
157.32
248.95
207.45
14.83
160
320
161.04
259.30
216.08
15.22
170
338
164.76
269.91
224.92
15.61
180
356
168.47
280.77
233.97
16.00
190
374
172.46
291.96
243.30
16.39
200
392
175.84
303.46
252.88
16.78
210
410
179.51
315.31
262.76
17.17
220
428
183.17
327.54
272.94
17.56
230
446
186.82
340.14
283.45
17.95
240
464
190.45
353.14
294.28
18.34
250
482
194.08
366.53
305.44
18.73
Содержание L90
Страница 14: ...1 4 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 68: ...2 54 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 136: ...3 68 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 224: ...4 88 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 692: ...6 36 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 708: ...7 16 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 742: ...9 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 804: ...10 62 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 872: ...C 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 878: ...D 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 882: ...iv L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 900: ...xviii L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...