CHAPTER 5: SETTINGS
CONTROL ELEMENTS
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-385
5
Generally, this scheme uses an overreaching zone 2 distance element to essentially compare the direction to a fault at all
terminals of the line. Ground directional overcurrent functions available in the L90 can be used in conjunction with the
zone 2 distance element to key the scheme and initiate operation. This increases the coverage for high-resistance faults.
The scheme is intended for three-terminal and two-terminal applications with weak-infeed conditions. As a long reach of
the overreaching distance element can be required for three-terminal applications, transient blocking logic is provided for
both distance and ground directional overcurrent elements. In order to cope with weak-infeed conditions, an echo feature
is made available.
By default the scheme uses the reverse-looking zone 4 distance element to identify reverse faults. Additionally, reverse-
looking ground directional overcurrent functions can be used in conjunction with the zone 4.
For proper operation, the zone 2 and 4 phase and ground distance elements must be enabled, configured, and set per
rules of distance relaying. Enable the line pickup element, configure it, and set properly to detect line-end-open/weak-
infeed and undervoltage conditions. If used by the scheme, the selected ground directional overcurrent function(s) must be
enabled, configured, and set accordingly.
HYB POTT WEAK
INFEED: Enabled
Range: Disabled, Enabled, Custom
HYB POTT W/I COND:
Off
Range: FlexLogic operand
HYB POTT RX PICKUP
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
TRANS BLOCK PICKUP
DELAY: 0.020 s
Range: 0.000 to 65.535 s in steps of 0.001
TRANS BLOCK RESET
DELAY: 0.090 s
Range: 0.000 to 65.535 s in steps of 0.001
ECHO DURATION:
0.100 s
Range: 0.000 to 65.535 s in steps of 0.001
ECHO LOCKOUT:
0.250 s
Range: 0.000 to 65.535 s in steps of 0.001
HYB POTT SEAL-IN
DELAY: 0.010 s
Range: 0.000 to 65.535 s in steps of 0.001
GND DIR O/C FWD:
Off
Range: FlexLogic operand
GND DIR O/C REV:
Off
Range: FlexLogic operand
HYB POTT NO OF COMM
BITS: 1
Range: 1, 2, or 4
HYB POTT RX1:
Off
Range: FlexLogic operand
HYB POTT RX2:
Off
Range: FlexLogic operand
HYB POTT RX3:
Off
Range: FlexLogic operand
HYB POTT RX4:
Off
Range: FlexLogic operand
HYB POTT SCHEME
TARGET: Self-Reset
Range: Self-Reset, Latched, Disabled
HYB POTT EVENT:
Disabled
Range: Disabled, Enabled
Содержание L90
Страница 14: ...1 4 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 68: ...2 54 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 136: ...3 68 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 224: ...4 88 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 692: ...6 36 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 708: ...7 16 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 742: ...9 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 804: ...10 62 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 872: ...C 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 878: ...D 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 882: ...iv L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 900: ...xviii L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...