L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CONTROL ELEMENTS
CHAPTER 5: SETTINGS
5
5.8.8 Synchrocheck (ANSI 25)
SETTINGS
CONTROL ELEMENTS
SYNCHROCHECK
SYNCHROCHECK 1(10)
The synchronism check function supervises the paralleling of two parts of a system that are to be joined by the closure of
a circuit breaker. The synchrocheck elements are typically used at locations where the two parts of the system are
interconnected through at least one other point in the system.
SYNCHROCHECK 1
SYNCHK1 FUNCTION:
Disabled
Range: Disabled, Enabled
SYNCHK1 BLOCK:
Off
Range: FlexLogic operand
SYNCHK1 V1 SOURCE:
SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
SYNCHK1 V2 SOURCE:
SRC 2
Range: SRC 1, SRC 2, SRC 3, SRC 4
SYNCHK1 MAX VOLT
DIFF: 10000 V
Range: 0 to 400000 V in steps of 1
SYNCHK1 MAX ANGLE
DIFF: 30°
Range: 0 to 100° in steps of 1
SYNCHK1 MAX FREQ
DIFF: 1.00 Hz
Range: 0.00 to 2.00 Hz in steps of 0.01
SYNCHK1 MAX FREQ
HYSTERESIS: 0.06 Hz
Range: 0.00 to 0.10 Hz in steps of 0.01
SYNCHK1 SYNC CLOSE:
Off
Range: FlexLogic operand
SYNCHK1 S-CLS MAX
dF: 0.50 Hz
Range: 0.10 to 2.00 Hz in steps of 0.01
SYNCHK1 S-CLS MIN
dF: 0.10 Hz
Range: 0.01 to 1.00 Hz in steps of 0.01
SYNCHK1 S-CLS BRK
TIME: 0.035 s
Range: 0.010 to 0.500 s in steps of 0.001
SYNCHK1 V2 MAG CORR
FACTOR: 1.00
Range: 0.10 to 10.00 in steps of 0.01
SYNCHK1 V2 ANGLE
SHIFT: 0
Range: -180 to +180 degrees in steps of 1
SYNCHK1 DEAD SOURCE
SELECT: LV1 and DV2
Range: None, LV1 and DV2, DV1 and LV2, DV1 or DV2,
DV1 Xor DV2, DV1 and DV2
SYNCHK1 DEAD V1
MAX VOLT: 0.30 pu
Range: 0.04 to 1.25 pu in steps of 0.01
SYNCHK1 DEAD V2
MAX VOLT: 0.30 pu
Range: 0.04 to 1.25 pu in steps of 0.01
SYNCHK1 LIVE V1
MIN VOLT: 0.70 pu
Range: 0.04 to 1.25 pu in steps of 0.01
SYNCHK1 LIVE V2
MIN VOLT: 0.70 pu
Range: 0.04 to 1.25 pu in steps of 0.01
SYNCHK1 TARGET:
Self-reset
Range: Self-reset, Latched, Disabled
SYNCHK1 EVENTS:
Disabled
Range: Disabled, Enabled
Содержание L90
Страница 14: ...1 4 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 68: ...2 54 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 136: ...3 68 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 224: ...4 88 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 692: ...6 36 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 708: ...7 16 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 742: ...9 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 804: ...10 62 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 872: ...C 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 878: ...D 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 882: ...iv L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 900: ...xviii L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...