5-356
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CONTROL ELEMENTS
CHAPTER 5: SETTINGS
5
5.8.11.3 Breaker flashover
SETTINGS
CONTROL ELEMENTS
MONITORING ELEMENTS
BREAKER FLASHOVER 1(2)
The detection of the breaker flashover is based on the following conditions:
•
Breaker open,
•
Voltage difference drop, and
•
Measured flashover current through the breaker
Furthermore, the scheme is applicable for cases where either one or two sets of three-phase voltages are available across
the breaker.
Three VT breaker flashover application
When only one set of VTs is available across the breaker, set the
BRK 1 FLSHOVR SIDE 2 SRC
setting to “None.” To detect an
open breaker condition in this application, the scheme checks if the per-phase voltages were recovered (picked up), the
status of the breaker is open (contact input indicating the breaker status is off), and no flashover current is flowing. A
contact showing the breaker status must be provided to the relay. The voltage difference is not considered as a condition
for open breaker in this part of the logic.
BREAKER
FLASHOVER 1
BKR 1 FLSHOVR
FUNCTION: Disabled
Range: Disabled, Enabled
BKR 1 FLSHOVR SIDE 1
SRC: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
BKR 1 FLSHOVR SIDE 2
SRC: None
Range: None, SRC 1, SRC 2, SRC 3, SRC 4
BKR 1 STATUS CLSD A:
Off
Range: FlexLogic operand
BKR 1 STATUS CLSD C:
Off
Range: FlexLogic operand
BKR 1 FLSHOVR V PKP:
0.850 pu
Range: 0.004 to 1.500 pu in steps of 0.001
BKR 1 FLSHOVR DIFF V
PKP: 1000 V
Range: 0 to 100000 V in steps of 1
BKR 1 FLSHOVR AMP
PKP: 0.600 pu
Range: 0.020 to 1.500 pu in steps of 0.001
BKR 1 FLSHOVR PKP
DELAY: 0.100 s
Range: 0.000 to 65.535 s in steps of 0.001
BKR 1 FLSHOVR SPV A:
Off
Range: FlexLogic operand
BKR 1 FLSHOVR SPV C:
Off
Range: FlexLogic operand
BKR 1 FLSHOVR BLOCK:
Off
Range: FlexLogic operand
BKR 1 FLSHOVR
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
BKR 1 FLSHOVR
EVENTS: Disabled
Range: Disabled, Enabled
Содержание L90
Страница 14: ...1 4 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 68: ...2 54 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 136: ...3 68 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 224: ...4 88 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 692: ...6 36 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 708: ...7 16 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 742: ...9 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 804: ...10 62 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 872: ...C 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 878: ...D 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 882: ...iv L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 900: ...xviii L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...