CHAPTER 2: PRODUCT DESCRIPTION
SPECIFICATIONS
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
2-49
2
2.6.9 Inter-relay communications
SHIELDED TWISTED-PAIR INTERFACE OPTIONS
LINK POWER BUDGET AND MAXIMUM OPTICAL INPUT POWER
The following specifications apply to filter interface modules manufactured from January 2012.
The following specifications apply to filter interface modules implemented before January 2012.
Interface type
Typical distance
RS422
1200 m
G.703
100 m
RS422 distance is based on transmitter power and does not take into consideration the clock source provided by
the user.
Emitter, fiber type
Cable type
Transmit power Received
sensitivity
Power budget Maximum
optical input
power
820 nm, Multimode
62.5/125
μ
m
-16 dBm
-32 dBm
16 dBm
-8 dBm
50/125
μ
m
-20 dBm
12 dBm
1300 nm, Multimode 62.5/125
μ
m
-16 dBm
-32 dBm
16 dBm
-8 dBm
50/125
μ
m
-20 dBm
12 dBm
1300 nm, Single
mode
9/125
μ
m
-15 dBm
-32 dBm
17 dBm
-8 dBm
1300 nm Laser,
Single mode
9/125
μ
m
0 dBm
-34 dBm
34 dBm
-8 dBm
1550 nm Laser,
Single mode
9/125
μ
m
5 dBm
-34 dBm
39 dBm
-10 dBm
Emitter, fiber type
Transmit
power
Received
sensitivity
Power budget Maximum optical
input power
820 nm LED, Multimode
–20 dBm
–30 dBm
10 dB
–7.6 dBm
1300 nm LED, Multimode
–21 dBm
–30 dBm
9 dB
–11 dBm
1300 nm ELED, Single mode
–23 dBm
–32 dBm
9 dB
–14 dBm
1300 nm Laser, Single mode
–1 dBm
–30 dBm
29 dB
–14 dBm
1550 nm Laser, Single mode
+5 dBm
–30 dBm
35 dB
–14 dBm
The power budgets are calculated from the manufacturer’s worst-case transmitter power and worst case receiver
sensitivity.
The power budgets for the 1300 nm ELED are calculated from the manufacturer's transmitter power and receiver
sensitivity at ambient temperature. At extreme temperatures these values deviate based on component tolerance.
On average, the output power decreases as the temperature is increased by a factor of 1 dB / 5 °C.
Содержание L90
Страница 14: ...1 4 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 68: ...2 54 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 136: ...3 68 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 224: ...4 88 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 692: ...6 36 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 708: ...7 16 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 742: ...9 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 804: ...10 62 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 872: ...C 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...