GE Power Management
ALPS Advanced Line Protection System
B-11
APPENDIX B
B.2 REGISTER MAPS
B
3290
Z4TIMETRIP
R/W
Unsigned Int
1
0=No, 1=Yes
-
0
3291
Z1PHASTRIP
R/W
Unsigned Int
1
0=No, 1=Yes
-
0
3292
ANYZ2PHASE
R/W
Unsigned Int
1
0=No, 1=Yes
-
0
3293
CONFGTRIP
R/W
Unsigned Int
1
0=No, 1=Yes
-
0
PROTECTION SETTINGS: LINE PICKUP
3294
LINEPICKUP
R/W
Unsigned Int
1
0=No, 1=Yes
-
0
3295
BYPASSTL3
R/W
Unsigned Int
1
0=No, 1=Yes
-
0
3296
I1PICKUP
R/W
P10
1
2 to 30
10 to 150
A
20
100
3297
REMOTEOPEN
R/W
Unsigned Int
1
0=No, 1=Yes
-
0
3298
TL20PICKUP
R/W
Unsigned Int
1
10 to 100
ms
-
PROTECTION SETTINGS: LINE OVERLOAD
3299
LINEOVERLD
R/W
Unsigned Int
1
0=No, 1=Yes
-
0
3300
LEVEL1PU
R/W
P10
1
5 to 40
25 to 200
A
20
100
3301
LEVEL2PU
R/W
P10
1
10 to 80
50 to 400
A
40
200
3302
LEVEL1TDLY
R/W
Unsigned Int
1
10 to 200
sec.
50
3303
LEVEL2TDLY
R/W
Unsigned Int
1
10 to 99
sec.
25
PROTECTION SETTINGS: SCHEME
3304
PICKSCHEME
R/W
Unsigned Int
1
0 =STEPDST, 1=PUTT,
2=POTT1, 3=POTT2,
4=HYBRID, 5=BLOCK,
6=HYBRID BLOCK
-
0
3305
NUMRCVR
R/W
Unsigned Int
1
0, 1, 2
-
0
3306
TRIPMODE
R/W
Unsigned Int
1
0=3POLE, 1=1POLE,
2=1POLEZ2
-
0
3307
CARRSTART
R/W
Unsigned Int
1
0=DIR, 1=IPB, 2=FD
-
1
3308
WKINFTRIP
R/W
Unsigned Int
1
0=No, 1=Yes
-
0
PROTECTION SETTINGS: SCHEME TIMERS
3309
TL1PICKUP
R/W
Unsigned Int
1
1 to 200
ms
5
3310
TL4PICKUP
R/W
Unsigned Int
1
0 to 50
ms
0
3311
TL4DROPOUT
R/W
Unsigned Int
1
0 to 50
ms
0
3312
TL5PICKUP
R/W
Unsigned Int
1
0 to 200
ms
50
3313
TL5DROPOUT
R/W
Unsigned Int
1
0 to 200
ms
50
3314
TL6PICKUP
R/W
Unsigned Int
1
0 to 200
ms
50
3315
TL6DROPOUT
R/W
Unsigned Int
1
0 to 200
ms
50
3316
TL16PICKUP
R/W
Unsigned Int
1
8 to 99
ms
8
3317
TL24DROPOUT
R/W
Unsigned Int
1
30 to 500
ms
30
3318
TL25DROPOUT
R/W
Unsigned Int
1
30 to 500
ms
30
3319
TL26PICKUP
R/W
Unsigned Int
1
0 to 50
ms
0
PROTECTION SETTINGS: LINE INFORMATION
3320
POSSEQANG
R/W
Unsigned Int
1
25 to 90
deg
85°
3321
ZERSEQANG
R/W
Unsigned Int
1
25 to 90
deg
75°
3322
ZLINE
R/W
P100
1
5 to 25000
1 to 5000
Ω
3000
600
3323
ZEROSEQK0
R/W
P100
1
100 to 700
-
300
3324
LINELENGTH
R/W
P10
1
0 to 5000
mi/km
1000
3325
LINEUNIT
R/W
Unsigned Int
1
0=Miles, 1=Km
-
0
3326
CTRATIO
R/W
Unsigned Int
1
1 to 5000
-
2000
400
3327
VTRATIO
R/W
Unsigned Int
1
1 to 7000
-
3000
Table B–4: MODBUS MEMORY MAP (Sheet 7 of 10)
ALPS
REGISTER
CONTENTS
TYPE
FORMAT
NO. OF
REGS.
RANGE
UNITS
DEFAULT
1 A
5 A
1 A
5 A
1, 2, 3, 4, 5, 6, 7, 8
See page B–14 for footnote explanations.
Содержание ALPS
Страница 2: ......
Страница 4: ......
Страница 182: ...5 20 ALPS Advanced Line Protection System GE Power Management 5 5 MOB TESTING 5 FUNCTIONAL TESTS FACTORY SETTINGS 5 ...
Страница 200: ...6 18 ALPS Advanced Line Protection System GE Power Management 6 5 ZONE REACH TESTS 6 FUNCTIONAL TESTS USER SETTINGS 6 ...
Страница 346: ...D 4 ALPS Advanced Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 352: ...F 2 ALPS Advanced Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 366: ...xiv ALPS Advanced Line Protection System GE Power Management INDEX INDEX ...