GE Power Management
ALPS Advanced Line Protection System
1-1
1 PRODUCT DESCRIPTION
1.1 GETTING STARTED
1
1 PRODUCT DESCRIPTION 1.1 GETTING STARTED
1.1.1 INSPECTION
Before attempting to install or use this relay, it is imperative that all WARNINGS and CAUTIONS in this man-
ual are reviewed to help prevent personal injury, equipment damage, and/or downtime.
Unpack the relay, the mounting brackets, and the hardware for attaching the mounting brackets to the sides of the relay.
Examine the relay for any damage sustained in transit, and if damage is evident, notify the shipping company and the near-
est GE Power Management sales office immediately.
Prior to applying power, ensure that the model number of the relay listed on the front panel corresponds to the model
ordered. Make sure that the DC supply power matches the rated voltage listed on the front panel. Refer to the elementary
diagrams on pages 1–49 to 1–52 for the locations of the DC power inputs
Instructions on using the keypad to change settings and put the relay into test mode can be found in Section 4.1.7: SET-
TING CHANGES on page 4–3. Complete instructions on operating the keypad are found in Chapter 8: LOCAL USER
INTERFACE.
GE Power Management contact information:
GE Power Management
215 Anderson Avenue
Markham, Ontario
Canada L6E 1B3
Telephone:
Toll Free North America:
(800) 547-8629
Europe
+34 94 485 88 54
Other Areas
(905) 294-6222
Emergency
(416) 414-4941
Fax:
(905) 201-2098
Email:
Home Page:
www.GEindustrial.com/pm
1.1.2 PASSWORDS, FACTORY SET
The ALPS requires passwords to change settings or perform actions. No password is required to obtain information from
the relay, including viewing the existing settings. The relay is shipped from the factory with the following MMI passwords:
SETTINGS: 123.
ACTIONS: 456.
MASTER: 789.
The decimal point following the digits is part of the password. Factory passwords MUST be changed
before the user can modify settings or initiate Actions.
In order to change the default password, follow these steps:
1.
Press the ACTIONS key [ACT].
2.
Press the ENTER key [ENT].
3.
Scroll to the CHANGE PASSWORD option.
4.
Select the Password Privilege level to be changed.
5.
Press [ENT].
6.
Enter the factory password (for example: 789. for Master Password).
7.
Enter your password.
8.
Re-enter your password.
9.
Press [END], press [ENT], and then press [CLR].
The keypad passwords stored in the relay may be viewed, in encoded format, via remote communications.
NOTE
NOTE
Содержание ALPS
Страница 2: ......
Страница 4: ......
Страница 182: ...5 20 ALPS Advanced Line Protection System GE Power Management 5 5 MOB TESTING 5 FUNCTIONAL TESTS FACTORY SETTINGS 5 ...
Страница 200: ...6 18 ALPS Advanced Line Protection System GE Power Management 6 5 ZONE REACH TESTS 6 FUNCTIONAL TESTS USER SETTINGS 6 ...
Страница 346: ...D 4 ALPS Advanced Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 352: ...F 2 ALPS Advanced Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 366: ...xiv ALPS Advanced Line Protection System GE Power Management INDEX INDEX ...