6-6
ALPS Advanced Line Protection System
GE Power Management
6.3 MEASURING UNIT TESTS
6 FUNCTIONAL TESTS (USER SETTINGS)
6
6.3 MEASURING UNIT TESTS
6.3.1 WARNING
The A1 contact will chatter when the unit under test is near its threshold.
Do not allow this to continue!
Remove the test current. A single contact closure is enough to determine that the unit has picked up.
At the start of each test is an area to record your specific setting for the function under test.
6.3.2 T5 – I
T
TRIP SUPERVISION TEST
1.
Protection Settings:
CURSUPVISN
(501)
IT_PICKUP = [_________] amps,
where
I
T
is set as follows:
I
T
=
I
A
,
I
B
, or
I
C
(eq.
6–1)
The test current,
I
op
, is single-phase and is applied to
I
A
. The ALPS should pick up when
I
op
is equal to
I
T
.
2.
Connect the relay as shown in Figure 4–3: PHASE TO GROUND TEST CONNECTIONS on page 4–12.
3.
Set the relay into test mode 34 (IT Detector). The LUI display contains: IT DETECTOR ON
4.
Set the level of
I
op
to
I
T
+ 0.1 = [_________] amps rms and apply to the relay. The A1 contact should close. Lower
I
op
to
I
T
– 0.1 = [_________] amps rms; the A1 contact should open.
5.
Reduce
I
op
to zero.
6.3.3 T6 – I
B
BLOCKING SUPERVISION TEST (BLOCKING SCHEMES)
1.
Protection Settings:
Z2DISTANCE
(205)
Z2GRDCHAR = GDOC
CURSUPVISN
(502)
IB_PICKUP = [_________] amps
SCHEME
(1201) PICKSCHEME = BLOCK
where
I
T
is set as follows:
, or
I
C
(eq. 6–2)
The test current,
I
op
, is single-phase and is applied to
I
A
. The ALPS should pick up when
I
op
is equal to
I
B
.
2.
Connect the relay as shown in Figure 4–3: PHASE TO GROUND TEST CONNECTIONS on page 4–12.
3.
Set the relay into test mode 35 (
I
B
Detector). The LUI display contains: IB DETECTOR ON
4.
Set the level of
I
op
to
I
B
+ 0.1 = [_________] amps rms and apply to the relay. The A1 contact should close. Lower
I
op
to
I
B
– 0.1 = [_________] amps rms; the A1 contact should open.
5.
Reduce
I
op
to zero.
6.3.4 T7 – GROUND DIRECTIONAL TRIP TEST, IPT + NT
This test applies to blocking schemes only.
1.
Protection Settings:
Z2DISTANCE
(205)
Z2GRDCHAR = GDOC
CURSUPVISN
(503)
IPT_PICKUP = [_________] amps
CAUTION
I
T
I
A
I
B
,
=
NOTE
Содержание ALPS
Страница 2: ......
Страница 4: ......
Страница 182: ...5 20 ALPS Advanced Line Protection System GE Power Management 5 5 MOB TESTING 5 FUNCTIONAL TESTS FACTORY SETTINGS 5 ...
Страница 200: ...6 18 ALPS Advanced Line Protection System GE Power Management 6 5 ZONE REACH TESTS 6 FUNCTIONAL TESTS USER SETTINGS 6 ...
Страница 346: ...D 4 ALPS Advanced Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 352: ...F 2 ALPS Advanced Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 366: ...xiv ALPS Advanced Line Protection System GE Power Management INDEX INDEX ...