2-60
ALPS Advanced Line Protection System
GE Power Management
2.5 REFERENCE TABLES
2 CALCULATION OF SETTINGS
2
902
BYPASSTL3
Bypass Line Pickup Time Delay
NO, YES
NO
903
I1PICKUP
I1 Pickup
1.0 to 15.0 amps
step 0.1
0.2 to 3.0 amps
step 0.1
3.0 A at 5A
0.6 A at 1A
REMOTEOPEN (THREE-PHASE SYSTEMS ONLY)
1001
REMOTEOPEN
Select Remote Open Detector
NO, YES
NO
1002
TL20PICKUP
Remote Open Detector Time
Delay
10 to 100 msec. step 1
100 msec.
LINEOVERLD
1101
LINEOVERLD
Select Line Overload Protection
NO, YES
NO
1102
LEVEL1PU
Level 1 pickup current
2.5 to 20 amps
step 0.1
0.5 to 4.0 amps
step 0.1
10 A at 5A
2 A at 1A
1103
LEVEL2PU
Level 2 pickup current
5.0 to 40.0 amps
step 0.1
1.0 to 8.0 amps
step 0.1
20 A at 5A
4 A at 1A
1104
LEVEL1TDLY
Level 1 time delay
10 to 200 sec. step 1
50 sec.
1105
LEVEL2TDLY
Level 2 time delay
10 to 99 sec. step 1
25 sec.
SCHEME
1201
PICKSCHEME
Select a scheme logic
STEPDST, PUTT, POTT1, POTT2, HYBRID,
BLOCK, HYBRIDP
STEPDST
1202
NUMRCVR
Select a number of receivers
0, 1, 2, 4
0
1203ˆ
TRIPMODE
1-phase / 3-phase Trip Mode
3POLE, 1POLE, 1POLEZ2
3POLE
1204
CARRSTART
Select Function to use to Start
Carrier in BLOCKing scheme
DIR, IPB, FD
IPB
1205
WKINFTRIP
Select Weak Infeed Tripping for
HYBRID scheme
NO, YES
NO
SCHMTIMERS
1301
TL1PICKUP
Trip Integrator
1 to 200 msec. step 1
5 msec.
1302
TL4PICKUP
POTT Coord Timer PU
0 to 50 msec. step 1
0 msec.
1303
TL4DROPOUT
POTT Coord Timer DO
0 to 50 msec. step 1
0 msec.
1304
TL5PICKUP
BKR1 b sw Coord Timer PU
0 to 200 msec. step 1
50 msec.
1305
TL5DROPOUT
BKR1 b sw Coord Timer DO
0 to 200 msec. step 1
50 msec.
1306
TL6PICKUP
BKR2 b sw Coord Timer PU
0 to 200 msec. step 1
50 msec.
1307
TL6DROPOUT
BKR2 b sw Coord Timer DO
0 to 200 msec. step 1
50 msec.
1308
TL16PICKUP
Weak Infeed Trip Timer
8 to 99 msec. step 1
8 msec.
1309
TL24DRPPOUT
GDOC Blocking Timer
30 to 500 msec. step 1
30 msec.
1310
TL25DRPOUT
Distance Blocking Timer
30 to 500 msec. step 1
30 msec.
1311
TL26PICKUP
Repeat Delay Timer
0 to 50 msec. step 1
0 msec.
LINE INFO
1401
POSSEQANG
Positive Sequence Impedance
Angle
25 to 90 deg. step 1
85 deg.
1402
ZERSEQANG
Zero Sequence Impedance Angle
25 to 90 deg. step 1
75 deg.
1403
ZLINE
Positive Sequence Line
Impedance in sec.ohms
0.01 to 50.0 ohms
step 0.01
0.05 to 250.0 ohms
step 0.05
6
Ω
at 5A
30
Ω
at 1A
1404
ZEROSEQK0
Z0/Z1 Ratio
1.0 to 7.0 step 0.01
3.0
1405
LINELENGTH
Line Length
0.0 to 500.0 step 0.1
100.0
1406
LINEUNIT
Units of Length
MILES, KM, PERCENT
MILES
1407
CTRATIO
CT Ratio
1 to 5000 step 1
400 for 5A
2000 for 1A
1408
PTRATIO
PT Ratio
1 to 7000 step 1
3000
Table 2–11: PROTECTION SETTINGS GUIDE (Sheet 4 of 7)
NO.
MNEMONIC
DESCRIPTION
RANGE (5A)
RANGE (1A)
DEFAULT
† Setting value QUAD applies to Revision B models only.
‡ Setting applicable to Revision B models only.
^ Setting applicable to Single Phase Tripping models only.
Содержание ALPS
Страница 2: ......
Страница 4: ......
Страница 182: ...5 20 ALPS Advanced Line Protection System GE Power Management 5 5 MOB TESTING 5 FUNCTIONAL TESTS FACTORY SETTINGS 5 ...
Страница 200: ...6 18 ALPS Advanced Line Protection System GE Power Management 6 5 ZONE REACH TESTS 6 FUNCTIONAL TESTS USER SETTINGS 6 ...
Страница 346: ...D 4 ALPS Advanced Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 352: ...F 2 ALPS Advanced Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 366: ...xiv ALPS Advanced Line Protection System GE Power Management INDEX INDEX ...