GE Power Management
ALPS Advanced Line Protection System
2-57
2 CALCULATION OF SETTINGS
2.5 REFERENCE TABLES
2
2.5.2 PROTECTION SETTINGS GUIDE
Table 2–11: PROTECTION SETTINGS GUIDE (Sheet 1 of 7)
NO.
MNEMONIC
DESCRIPTION
RANGE (5A)
RANGE (1A)
DEFAULT
Z1 DISTANCE
101
Z1PHASE
Z1 Phase Distance
NO, YES
YES
102
Z1PHREACH
Z1 Phase Reach
0.01 to 50.0 ohms
step 0.01
0.05 to 250.0 ohms
step 0.05
5.40
Ω
at 5A
27.0
Ω
at 1A
103
Z1PLEVDET
Z1 Phase Level Detector (Series
Capacitor Model Only)
0.0 to 9.9 p.u. volts step 0.1
0
104
Z1GROUND
Z1 Ground Distance
NO, YES
YES
105
Z1GRDREACH
Z1 Ground Reach
0.01 to 50.0 ohms
step 0.01
0.05 to 250.0 ohms
step 0.05
5.40
Ω
at 5A
27.0
Ω
at 1A
106
Z1GRDCHAR
Z1 Ground Characteristic
MHO, REACT, QUAD
†
MHO
107
Z1SUREACH
Z1 Ground Reaction Mho
Supervision Reach
0.01 to 50.0 ohms
step 0.01
0.05 to 250 ohms
step 0.05
20.0
Ω
at 5A
100
Ω
at 1A
108
Z1GROUNDK0
Z1 Ground K0
1.0 to 7.0 step 0.01
2.7
109
Z1GLEVDET
Z1 Ground Level Detector (Series
Capacitor Model Only)
0.0 to 9.9 p.u. volts step 0.1
0 V
110
Z1BLOCK
Blocking Supervision of Z1
NO, YES
NO
111
‡
Z1GCHARANG
Z1 Ground Characteristic Timer
Angle
80° to 155° step 1
90°
112
‡
Z1RGREACH
Z1 Resistive Ground Reach
0.01 to 100.00
Ω
step 0.01
0.05 to 500
Ω
step 0.01
8.1
Ω
at 5A
40.5
Ω
at 1A
Z2DISTANCE
201
Z2PHASE
Z2 Phase Distance
NO, YES
YES
202
Z2PHREACH
Z2 Phase Reach
0.01 to 50.0 ohms
step 0.01
0.05 to 250.0 ohms
step 0.05
9.00
Ω
at 5A
45.0
Ω
at 1A
203
Z2PCHARANG
Z2 Phase Characteristic Angle
90 to 120° step 5
90 deg.
204
Z2GROUND
Z2 Ground Distance
NO, YES
YES
205
Z2GRDCHAR
Z2 Ground Characteristic
MHO, GDOC, MHOGDOC, MHO2GDOC,
QUAD
†
MHO
206
Z2GRDREACH
Z2 Ground Reach
0.01 to 50.0 ohms
step 0.01
0.05 to 250.0 ohms
step 0.05
9.00
Ω
at 5A
45.0
Ω
at 1A
207
Z2GCHARANG
Z2 Ground Characteristic Angle
80 to 155 deg. step 5
90 deg.
208
Z2TIMERS
Z2 Timers
NO, YES
YES
209
Z2P_TIME
Z2 Phase Timer
0.10 to 3.0 sec. step 0.01
1.0 sec.
210
Z2G_TIME
Z2 Ground Timer
0.10 to 3.0 sec. step 0.01
1.0 sec.
211
‡
Z2RGREACH
Zone 2 Resistive Ground Reach
0.01 to 100.00
Ω
step 0.01
0.05 to 500
Ω
step 0.01
13.5
Ω
at 5A
67.5
Ω
at 1A
Z3DISTANCE
301
Z3PHASE
Z3 Phase Distance
NO, YES
YES
302
Z3PHREACH
Z3 Phase Reach
0.01 to 50.0 ohms
step 0.01
0.05 to 250.0 ohms
step 0.05
12.0
Ω
at 5A
60.0
Ω
at 1A
303
Z3PCHARANG
Z3 Phase Characteristic Angle
90 to 120 deg. step 5
90 deg.
304
Z3GROUND
Z3 Ground Distance
NO, YES
YES
305
Z3GRDREACH
Z3 Ground Reach
0.01 to 50.0 ohms
step 0.01
0.05 to 250.0 ohms
step 0.05
12.0
Ω
at 5A
60.0
Ω
at 1A
306
Z3GCHARANG
Z3 Ground Characteristic Angle
80 to 155 deg. step 5
90 deg.
307
Z3P_TIME
Z3 Phase Timer
0.10 to 10.0 sec. step 0.01
2.0 sec.
308
Z3G_TIME
Z3 Ground Timer
0.10 to 10.0 sec. step 0.01
2.0 sec.
309
‡
Z3GRDCHAR
Z3 Ground Characteristic
MHO, QUAD
MHO
† Setting value QUAD applies to Revision B models only.
‡ Setting applicable to Revision B models only.
^ Setting applicable to Single Phase Tripping models only.
Содержание ALPS
Страница 2: ......
Страница 4: ......
Страница 182: ...5 20 ALPS Advanced Line Protection System GE Power Management 5 5 MOB TESTING 5 FUNCTIONAL TESTS FACTORY SETTINGS 5 ...
Страница 200: ...6 18 ALPS Advanced Line Protection System GE Power Management 6 5 ZONE REACH TESTS 6 FUNCTIONAL TESTS USER SETTINGS 6 ...
Страница 346: ...D 4 ALPS Advanced Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 352: ...F 2 ALPS Advanced Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 366: ...xiv ALPS Advanced Line Protection System GE Power Management INDEX INDEX ...