4-8
ALPS Advanced Line Protection System
GE Power Management
4.2 GENERAL RELAY TESTS
4 ACCEPTANCE/PERIODIC TESTS
4
4.2.3 T2 – DIGITAL OUTPUT TEST
This test checks all outputs of the relay. It is a convenient way to determine proper system connections and verify the oper-
ation of all relay contacts, without having to apply currents and voltages to simulate faults. Protection can be enabled or dis-
abled, as deemed necessary.
If this test is run remotely through ALPS-Link, then switch RM BRKR must be in the down position to allow
the outputs to operate. Refer to Section 8.4.1: HARDWARE SWITCHES on page 8–24 for details on chang-
ing the switch position. Note that the relay is shipped from the factory with the switch in the down position
allowing the outputs to operate.
1.
Connect the relay as shown in Figure 4–1: DIGITAL OUTPUTS TEST CONNECTIONS on page 4–9.
2.
Press the [ACT] key and enter the control level password.
3.
Use the arrow key to select 8. Digital Output Test
4.
Press the [ENT] key. Before a contact is allowed to be tested, the display prompts DISABLE PROTECT?
5.
Press the [1/Y] key followed by the [ENT] key to turn protection off. Protection remains off until the test mode is ended
(if desired, protection can be left enabled during the test).
6.
Select the output to test by using the arrow keys to scroll to the desired output, such as T1, and press the [ENT] key.
When the digital output is chosen, the selected relay output closes. Verify that the output under test has closed, using
an ohmmeter or other suitable device.
7.
After the output is tested, scroll to the next output to test, then press the [ENT] key. This output closes and the previ-
ously selected output opens. Continue in this fashion until all outputs are tested.
8.
End the test mode by scrolling to the END TEST MODE selection, then press the [ENT] key. Alternatively, press [END]
followed by the [ENT] key to end the test and re-enable protection.
Table 4–2: DIGITAL OUTPUTS TEST CONNECTIONS
OUPTUT
X
Y
OUTPUT
X
Y
T1
A3
A19
A12
†
B4
B20
T2
A4
A20
KT1 (no)
B5
B21
T3
A5
A21
KT1 (nc)
B5
B22
T4
A6
A22
KT2 (no)
B5
B21
T5
†
A7
A23
KT2 (nc)
B23
B7
T6
†
A8
A24
KT3 (no)
B8
B24
A1
A9
A25
KT3 (nc)
B8
B25
A2
A10
A26
KT4 (no)
B26
B9
A3
A11
A27
KT4 (nc)
B26
B10
A4
A12
A28
C1A (no)
B11
B27
A5
A13
A29
C1B (nc)
B11
B28
A6
A14
A30
C2A (no)
B29
B12
A7
A15
A31
C2B (nc)
B29
B13
A8
A16
A32
CA (nc)
B14
B30
A9
†
B1
B17
CA (no)
B14
B31
A10
†
B2
B18
PWR (nc)
B32
B15
A11
†
B3
B19
PWR (no)
B32
B16
Tx - TRIPPING contacts (programmable)
Ax - Alarm contacts (programmable)
KTx - Key Transmitter contacts (programmable)
Cxy - C Form contacts with one NO/NC contact pair (programmable)
CA - Critical Alarm
PWR - Power Supply Alarm
†
These digital outputs apply to the Single Phase Tripping model only.
NOTE
Содержание ALPS
Страница 2: ......
Страница 4: ......
Страница 182: ...5 20 ALPS Advanced Line Protection System GE Power Management 5 5 MOB TESTING 5 FUNCTIONAL TESTS FACTORY SETTINGS 5 ...
Страница 200: ...6 18 ALPS Advanced Line Protection System GE Power Management 6 5 ZONE REACH TESTS 6 FUNCTIONAL TESTS USER SETTINGS 6 ...
Страница 346: ...D 4 ALPS Advanced Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 352: ...F 2 ALPS Advanced Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 366: ...xiv ALPS Advanced Line Protection System GE Power Management INDEX INDEX ...