1-10
ALPS Advanced Line Protection System
GE Power Management
1.3 CUSTOM PROGRAMMABILITY
1 PRODUCT DESCRIPTION
1
1.3.4 CONFIGURABLE OUTPUTS
All of the output relays in the ALPS, except for the alarm output relays, are user-configurable. However, each ALPS relay is
shipped with Default Output Relay Assignments. These are shown below and in Figure 1–28: ELEMENTARY DIAGRAM
WITH DEFAULT I/O (THREE PHASE TRIPPING) on page 1–50 for the three phase model and Figure 1–27: ELEMEN-
TARY DIAGRAM WITH DEFAULT I/O (SINGLE PHASE TRIPPING) on page 1–49 for the single phase model.
Table 1–5: ALPS DEFAULT OUTPUT CONTACT ASSIGNMENTS: SINGLE PHASE MODEL
RELAY
DESCRIPTION
MNEMONIC
INDEX NO.
T1
TRIP BUS PHASE A
TRIPA
33
T2
TRIP BUS PHASE A
TRIPA
33
T3
TRIP BUS PHASE A
TRIPA
33
T4
TRIP BUS PHASE A
TRIPA
33
T5
TRIP BUS PHASE B
TRIPB
34
T6
TRIP BUS PHASE C
TRIPC
34
A1
MANUAL CLOSE BREAKER 1
MNCLS1
58
A2
MANUAL CLOSE BREAKER 2
MNCLS2
59
A3
TRIP BUS PHASE A
TRIPA
33
A4
TRIP BUS PHASE A
TRIPA
33
A5
THREE PHASE RECLOSE INITIATE
RI-3P
37
A6
THREE PHASE RECLOSE INITIATE
RI-3P
37
A7
RECLOSE CANCEL OUTPUT FROM SCHEME LOGIC
CANCL
38
A8 to A12
UNASSIGNED
---
---
KT1
KEY TRANSMITTER 1 / CARRIER START #1
KEY1
39
KT2
KEY TRANSMITTER 2 / CARRIER STOP #1
KEY2
40
KT3
KEY TRANSMITTER 1 / CARRIER START #1
KEY1
39
KT4
KEY TRANSMITTER 2 / CARRIER START #2
KEY2
40
C1
NON-CRITICAL ALARM
NCALM
52
C2
PT FUSE FAILURE ALARM
FF
115
Table 1–6: ALPS DEFAULT OUTPUT CONTACT ASSIGNMENTS: THREE PHASE MODEL
RELAY
DESCRIPTION
MNEMONIC
INDEX NO.
T1
TRIP CIRCUIT #1
TRIPA
33
T2
TRIP CIRCUIT #2
TRIPA
33
T3
TRIP CIRCUIT #3
TRIPA
33
T4
TRIP CIRCUIT #4
TRIPA
33
A1
MANUAL CLOSE CIRCUIT BREAKER #1
MNCLS1
58
A2
MANUAL CLOSE CIRCUIT BREAKER #2
MNCLS2
59
A3
BREAKER FAILURE INITIATE #1
TRIPA
33
A4
BREAKER FAILURE INITIATE #2
TRIPA
33
A5
RECLOSE INITIATE #1
RI_3P
37
A6
RECL OSE INITIATE #2
R1_3P
37
A7
RECLOSE CANCEL
CANCL
38
A8
RECLOSE CANCEL
CANCL
38
KT1
KEY TRANSMITTER 1 / CARRIER START #1
KEY1
39
KT2
KEY TRANSMITTER 2 / CARRIER STOP #1
KEY2
40
KT3
KEY TRANSMITTER 1 / CARRIER START #1
KEY1
39
KT4
KEY TRANSMITTER 2 / CARRIER START #2
KEY2
40
C1
NON-CRITICAL ALARM
NCALM
52
C2
PT FUSE FAILURE ALARM
FF
115
Содержание ALPS
Страница 2: ......
Страница 4: ......
Страница 182: ...5 20 ALPS Advanced Line Protection System GE Power Management 5 5 MOB TESTING 5 FUNCTIONAL TESTS FACTORY SETTINGS 5 ...
Страница 200: ...6 18 ALPS Advanced Line Protection System GE Power Management 6 5 ZONE REACH TESTS 6 FUNCTIONAL TESTS USER SETTINGS 6 ...
Страница 346: ...D 4 ALPS Advanced Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 352: ...F 2 ALPS Advanced Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 366: ...xiv ALPS Advanced Line Protection System GE Power Management INDEX INDEX ...