GE Power Management
ALPS Advanced Line Protection System
B-7
APPENDIX B
B.2 REGISTER MAPS
B
2001
Date (Event 1)
RO
F1
2
MM/DD/YY
-
-
-
2003
Time (Event 1)
RO
F2
2
HH:MM:sec.ms
-
-
-
2005
Event Code (Event 1)
RO
F61
1
-
-
-
2006
Event Source (Event 1)
RO
F69
1
-
-
-
2007
Date (Event 2)
RO
F1
2
MM/DD/YY
-
-
-
2009
Time (Event 2)
RO
F2
2
HH:MM:sec.ms
-
-
-
2011
Event Code (Event 2)
RO
F61
1
-
-
-
2012
Event Source (Event 2)
RO
F69
1
-
-
-
2013
Date (Event 3)
RO
F1
2
MM/DD/YY
-
-
-
2015
Time (Event 3)
RO
F2
2
HH:MM:sec.ms
-
-
-
2017
Event Code (Event 3)
RO
F61
1
-
-
-
-
-
2018
Event Source (Event 3)
RO
F69
1
-
-
-
-
-
↓
↓
↓
-
-
-
-
-
-
-
2895
Date (Event 150)
RO
F1
2
MM/DD/YY
-
-
-
2897
Time (Event 150)
RO
F2
2
HH:MM:sec.ms
-
-
-
2899
Event Code (Event 150)
RO
F61
1
-
-
-
-
-
2900
Event Source (Event 150)
RO
F69
1
-
-
-
-
-
2901
Reserved
RO
-
-
-
-
-
-
-
↓
↓
RO
-
-
-
-
-
-
-
2999
Reserved
RO
-
-
-
-
-
-
-
SETTINGS REGISTERS GROUP 1
GENERAL SETTINGS: CONFIGURE
3000
Date
R/W
F1
2
MM/DD/YY
-
-
-
3002
Time
R/W
F2
2
HH:MM:sec.ms
-
-
-
3004
Reserved
-
-
-
-
-
-
-
-
↓
↓
-
-
-
-
-
-
-
-
3025
Reserved
-
-
-
-
-
-
-
-
3026
SYSFREQ
R/W
Integer
1
50, 60
Hz
60
3027
PHASEROTATE
R/W
Integer
1
0 = ABC; 1 = ACB
-
0
3028
TIMESYNCH
R/W
Integer
1
0 = internal, 1 = IRIG-B
-
0
3029
NUM_BKR
R/W
Integer
1
1, 2
-
1
3030
NUM_TC
R/W
Integer
1
1, 2
-
1
3031
NUM_MON
R/W
Integer
1
0 to 64 (1-phase)
0 to 16 (3-phase)
-
7 (1-phase)
0 (3-phase)
3032
DISPLAYVAL
R/W
F60
1
0 = Primary, 1 = Secondary
-
0
3033
LANGUAGE
R/W
Integer
1
0 = English, 1 = Spanish
GENERAL SETTINGS: COMMUNICATIONS PORTS
3035
COMPORT1
R/W
F12
1
-
-
-
9601
3036
COMPORT2
R/W
F13
1
-
-
-
09601
3037
COMPORT3
R/W
F13
1
-
-
-
09601
GENERAL SETTINGS: OSCILLOGRAPHY
3038
NUMFAULTS
R/W
Integer
1
2, 4, 8, 12 (std. mem)
6, 12, 24, 36 (exp.mem)
-
12
3039
PREFAULT
R/W
Integer
1
1 to 8
-
5
3040
SPLITREC
R/W
Integer
1
0 to 100
%
0%
GENERAL SETTINGS: BREAKER DUTY
Table B–4: MODBUS MEMORY MAP (Sheet 3 of 10)
ALPS
REGISTER
CONTENTS
TYPE
FORMAT
NO. OF
REGS.
RANGE
UNITS
DEFAULT
1 A
5 A
1 A
5 A
1, 2, 3, 4, 5, 6, 7, 8
See page B–14 for footnote explanations.
Содержание ALPS
Страница 2: ......
Страница 4: ......
Страница 182: ...5 20 ALPS Advanced Line Protection System GE Power Management 5 5 MOB TESTING 5 FUNCTIONAL TESTS FACTORY SETTINGS 5 ...
Страница 200: ...6 18 ALPS Advanced Line Protection System GE Power Management 6 5 ZONE REACH TESTS 6 FUNCTIONAL TESTS USER SETTINGS 6 ...
Страница 346: ...D 4 ALPS Advanced Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 352: ...F 2 ALPS Advanced Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 366: ...xiv ALPS Advanced Line Protection System GE Power Management INDEX INDEX ...