GE Power Management
ALPS Advanced Line Protection System
2-51
2 CALCULATION OF SETTINGS
2.5 REFERENCE TABLES
2
2.5 REFERENCE TABLES
2.5.1 INDEX NUMBERS
Table 2–9: INDEX NUMBERS – CONTACT CONVERTER INPUT ASSIGNMENT
ALPS with Single Phase Tripping
ALPS with Three Phase Tripping
Index
Description
Mnemonic
Index
Description
Mnemonic
1
Breaker #1 52b Contact Input Phase A
52B_1A
1
Breaker #1 52b Contact Input
52B_1
2
Breaker #1 52b Contact Input Phase B
52B_1B
2
Spare
3
Breaker #1 52b Contact Input Phase C
52B_1C
3
Spare
4
Breaker #2 52b Contact Input Phase A
52B_2A
4
Breaker #2 52b Contact Input
52B_2
5
Breaker #2 52b Contact Input Phase B
52B_2B
5
Spare
6
Breaker #2 52b Contact Input Phase C
52B_2C
6
Spare
7
Enable Three Phase Tripping
EXTRP3P
7
Spare
8
Change Setting Group Input (BIT0)
CGST1
8
Change Setting Group Input (BIT0)
CGST1
9
Change Setting Group Input (BIT1)
CGST2
9
Change Setting Group Input (BIT1)
CGST2
10
External Contact Input to Stop Carrier *
STCR
10
External Contact Input to Stop Carrier *
STCR
11
External Contact Input to Block Pilot
Tripping *
BPLTRP
11
External Contact Input to Block Pilot
Tripping*
BLPTRP
12
Receiver 1 Input
RCVR1
12
Receiver 1 Input
RCVR1
13
Receiver 2 Input
RCVR2
13
Receiver 2 Input
RCVR2
14
External Reclose Initiate 1 Pole
EXRI1P
14
Spare
15
External Reclose Initiate 3 Pole
EXRI3P
15
External Reclose Initiate 3 Pole
EXRI3P
16
External Reclose Inhibit
EXRINH
16
External Reclose Inhibit
EXRINH
17
External Reclose Cancel
EXRCNL
17
External Reclose Cancel
EXRCNL
18
Reclose Reset
RCLRST
18
Reclose Reset
RCLRST
19
External Phase 3 Reclose
CLOS3P
19
Spare
20
External Contact Input to Reset ALPS
Trip Target Display
RESET
20
Spare
21
Spare
21
Spare
22
External Contact Input to Disable
Outputs
DISOUT
22
External Contact Input to Disable
Outputs
DISOUT
23
External Contact Input to Trigger
Oscillography Capture
OSCTRG
23
External Contact Input to Trigger
Oscillography Capture
OSCTRG
24
Manual Lockout
MANLKT
24
Manual Lockout
MANLLT
25
CONFIGURABLE INPUT1
CNFDI1
25
CONFIGURABLE INPUT1
CNFDI1
26
CONFIGURABLE INPUT2
CNFDI2
26
CONFIGURABLE INPUT2
CNFDI2
27
CONFIGURABLE INPUT3
CNFDI3
27
CONFIGURABLE INPUT3
CNFDI3
28
CONFIGURABLE INPUT4
CNFDI4
28
CONFIGURABLE INPUT4
CNFDI4
29
CONFIGURABLE INPUT5
CNFDI5
29
CONFIGURABLE INPUT5
CNFDI5
30
CONFIGURABLE INPUT6
CNFDI6
30
CONFIGURABLE INPUT6
CNFDI6
31
CONFIGURABLE INPUT7
CNFDI7
31
CONFIGURABLE INPUT7
CNFDI7
32
CONFIGURABLE INPUT8
CNFDI8
32
CONFIGURABLE INPUT8
CNFDI8
NOTE:
Any of the above signals (1 to 32) may be assigned to the 8 available ALPS Contact Converter Inputs (CC1 to CC8). Those 8
signals will also be available for use for the Programmable Outputs and/or the Configurable Logic. Unassigned signals will
NOT be available.
NOTE:
Contacts are normally open; add 1000 to number to close contact under normal conditions.
* Applies to Blocking Scheme Only
Содержание ALPS
Страница 2: ......
Страница 4: ......
Страница 182: ...5 20 ALPS Advanced Line Protection System GE Power Management 5 5 MOB TESTING 5 FUNCTIONAL TESTS FACTORY SETTINGS 5 ...
Страница 200: ...6 18 ALPS Advanced Line Protection System GE Power Management 6 5 ZONE REACH TESTS 6 FUNCTIONAL TESTS USER SETTINGS 6 ...
Страница 346: ...D 4 ALPS Advanced Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 352: ...F 2 ALPS Advanced Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 366: ...xiv ALPS Advanced Line Protection System GE Power Management INDEX INDEX ...