GE Power Management
ALPS Advanced Line Protection System
6-13
6 FUNCTIONAL TESTS (USER SETTINGS)
6.5 ZONE REACH TESTS
6
6.5.4 T13 – ZONE 2 GROUND REACH, MTG GROUND FAULTS
1.
Protection Settings:
Z2DISTANCE
(201)
Z2PHASE = NO
(204)
Z2GROUND = YES
(206)
Z2GRDREACH = [_________] ohms,
V
NOM
2
= [_________] V,
I
T
= [_________] A,
øI
2
= [_________]°,
2.
Connect the relay as shown in Figure 4–3: PHASE TO GROUND TEST CONNECTIONS on page 4–12 for the appro-
priate phase under test.
3.
Set the relay to the Zone 2 ground test mode for the appropriate phase under test. The LUI displays, for instance,
ZONE 2 AG ON
4.
Set the voltage inputs as follows: VA: 67 V rms
∠
0°, VB: 67 V rms
∠
–120°, VC: 67 V rms
∠
–240°.
5.
Set the fault current,
I
op
, phase angle to
øI = [________]°, lagging.
6.
Set the fault current to
I
T
= [________] amps rms. Reduce the voltage of the faulted phase and check that the A1 con-
tact closes when the voltage is within 7% of
V
NOM
.
7.
Reduce the fault current to zero.
8.
Return Zone 2 phase, Z2PHASE, to your specific setting.
6.5.5 T14 – ZONE 3 GROUND REACH, M3G GROUND FAULTS
1.
Protection Settings:
Z3DISTANCE
(301)
Z3PHASE = NO
(304)
Z3GRND = YES
(305)
Z3GRDREACH = [_________] ohms,
V
NOM
3
= [_________] V,
I
T
= [_________] A,
øI
3
= [_________]°,
2.
Connect the relay as shown in Figure 4–3: PHASE TO GROUND TEST CONNECTIONS for the appropriate phase
under test.
3.
Set the relay to the Zone 3 ground test mode for the appropriate phase under test. The LUI displays, for instance:
ZONE 3 AG ON
4.
Set the voltage inputs as follows: VA: 67 V rms
∠
0°, VB: 67 V rms
∠
–120°, VC: 67 V rms
∠
–240°.
5.
Set the fault current,
I
op
, phase angle to
øI = [________]°, lagging.
6.
Set the fault current to
I
T
= [________] amps rms. Reduce the voltage of the faulted phase and check that the A1 con-
tact closes when the voltage is within 7% of
V
NOM
.
7.
Reduce the fault current to zero.
8.
Return Zone 3 phase, Z3PHASE, to your specific setting.
Содержание ALPS
Страница 2: ......
Страница 4: ......
Страница 182: ...5 20 ALPS Advanced Line Protection System GE Power Management 5 5 MOB TESTING 5 FUNCTIONAL TESTS FACTORY SETTINGS 5 ...
Страница 200: ...6 18 ALPS Advanced Line Protection System GE Power Management 6 5 ZONE REACH TESTS 6 FUNCTIONAL TESTS USER SETTINGS 6 ...
Страница 346: ...D 4 ALPS Advanced Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 352: ...F 2 ALPS Advanced Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 366: ...xiv ALPS Advanced Line Protection System GE Power Management INDEX INDEX ...