GE Power Management
ALPS Advanced Line Protection System
5-9
5 FUNCTIONAL TESTS (FACTORY SETTINGS)
5.3 ZONE REACH AND TIMER TESTS
5
7.
Reduce the fault current to zero. Note that the trip target indication concurs with the fault. An AG fault is displayed as
TRIP: AG Z1 "DIST", where “DIST” is the displayed target.
8.
Repeat the test for BG and CG faults.
5.3.3 T12 – ZONE 2 GROUND REACH, MTG GROUND FAULTS
1.
Protection settings:
Z1DISTANCE
(101)
Z1PHASE = NO
(104)
Z1GROUND = NO
Z2DISTANCE
(201)
Z2PHASE = NO
(204)
Z2GROUND = YES
Z3DISTANCE
(301)
Z3PHASE = NO
(304)
Z3GRND = NO
Z4DISTANCE
(401)
Z4PHASE = NO
(405)
Z4GRND = NO
2.
Connect the relay as shown in Figure 4–3: PHASE TO GROUND TEST CONNECTIONS on page 4–12 for the appro-
priate phase under test.
3.
Set the relay to test mode 15 (Any Zone 2 Ground). The LUI displays: ANY Z2 GRND ON
4.
Set the voltage inputs to the following values:
VA: 67 volts rms
∠
0°,
VB: 67 volts rms
∠
–120°,
VC: 67 volts rms
∠
+120°.
5.
Set the fault current,
I
op
, to the phase-angle value listed below (increase VA, VB, and VC to 75 V when
∠
I
op
= –79°).
6.
Set the fault current to 4.6 (0.9) amps rms. Reduce the voltage of the faulted phase and check that the A1 contact
closes when the voltage is within the limits above.
7.
Reduce the fault current to zero. Note that the trip target indication concurs with the fault. An AG fault is displayed as
TRIP AG Z2 "DIST", where “DIST” is the displayed target.
8.
Repeat the test for BG and CG faults.
5.3.4 T13 – ZONE 3 GROUND REACH, M3G GROUND FAULTS
1.
Protection Settings:
Z1DISTANCE
(101)
Z1PHASE = NO
(104)
Z1GROUND = NO
Z2DISTANCE
(201)
Z2PHASE = NO
(204)
Z2GROUND = NO
∠
I DEGREES
VOLTS RMS
DISPLAYED TARGET
†
–49
56 to 63
–
–79
65 to 72
146 to 154
–109
56 to 63
–
†
Reference only
Содержание ALPS
Страница 2: ......
Страница 4: ......
Страница 182: ...5 20 ALPS Advanced Line Protection System GE Power Management 5 5 MOB TESTING 5 FUNCTIONAL TESTS FACTORY SETTINGS 5 ...
Страница 200: ...6 18 ALPS Advanced Line Protection System GE Power Management 6 5 ZONE REACH TESTS 6 FUNCTIONAL TESTS USER SETTINGS 6 ...
Страница 346: ...D 4 ALPS Advanced Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 352: ...F 2 ALPS Advanced Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 366: ...xiv ALPS Advanced Line Protection System GE Power Management INDEX INDEX ...