GE Power Management
ALPS Advanced Line Protection System
6-15
6 FUNCTIONAL TESTS (USER SETTINGS)
6.5 ZONE REACH TESTS
6
a) SETTINGS AND CALCULATIONS
1.
Record the following relay settings:
(1401), POSSEQANG = [________]
(102), Z1PRREACH = [________] (Zone 1)
(202), Z2PHREACH = [________] (Zone 2)
(302), Z3PHREACH = [________] (Zone 3)
(402), Z4PHREACH = [________] (Zone 4)
Z1PCHARANG = 90° (fixed for Zone 1)
(203), Z2PCHARANG = [________] (Zone 2)
(303), Z3PCHARANG = [________] (Zone 3)
(403), Z4PCHARANG = [________] (Zone 4)
2.
Determine the test current,
I
T
, for Zone 1, Zone 2, Zone 3, and Zone 4 from Table 6–2.
I
T
(Z1R) = [________] Amps rms
I
T
(Z2R) = [________] Amps rms
I
T
(Z3R) = [________] Amps rms
I
T
(Z4R) = [________] Amps rms
3.
Choose
øI (the I
T
angle).
V
NOM
is at maximum when
øI = øZ – 30°.
øI
1
= [________]° (Zone 1)
øI
2
= [________]° (Zone 2)
øI
3
= [________]° (Zone 3)
øI
4
= [________]° (Zone 4)
4.
Calculate
V
NOM
for each zone by substituting the values of
Z
R
,
øZ (POSSEQANG), I
T
, and
øI into Equations 25 and 26
for
V
NOM
according to zone.
V
NOM
1
= [________] Volts rms (nominal test voltage for Z1P)
V
NOM
2
= [________] Volts rms (nominal test voltage for Z2P)
V
NOM
3
= [________] Volts rms (nominal test voltage for Z3P)
V
NOM
4
= [________] Volts rms (nominal test voltage for Z4P)
If Zone 4 is reversed (Protection Setting 408: Z4DIRECTN = REVERS), remember to add 180° to both the test
current angle,
øI
4
, and the impedance angle,
øZ
4
. If Zone 4 has a non-zero offset, use the ALPS-Test software
to calculate
V
NOM
4
.
5.
Record
V
NOM
n
,
I
T
, and
øI
n
in the space provided in the appropriate Zone reach test.
Table 6–2: TEST CURRENT RANGES FOR PHASE-TO-PHASE REACH
Z
G
REACH
(
I
N
= 5 A)
I
T
(A)
Z
G
REACH
(
I
N
= 1 A)
I
T
(A)
0.1 to 2.5
10
0.5 to 12.5
2
2.5 to 6.0
8
12.5 to 30.0
2
6.0 to 12.0
5
30.0 to 60.0
1
12.0 to 20.0
3
60.0 to 100.0
0.6
20.0 to 30.0
2
100.0 to 150.0
0.4
30.0 to 40.0
1.5
150.0 to 200.0
0.3
40.0 to 50.0
1.0
200.0 to 250.0
0.2
NOTE
Содержание ALPS
Страница 2: ......
Страница 4: ......
Страница 182: ...5 20 ALPS Advanced Line Protection System GE Power Management 5 5 MOB TESTING 5 FUNCTIONAL TESTS FACTORY SETTINGS 5 ...
Страница 200: ...6 18 ALPS Advanced Line Protection System GE Power Management 6 5 ZONE REACH TESTS 6 FUNCTIONAL TESTS USER SETTINGS 6 ...
Страница 346: ...D 4 ALPS Advanced Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 352: ...F 2 ALPS Advanced Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 366: ...xiv ALPS Advanced Line Protection System GE Power Management INDEX INDEX ...