The digital signal processor (DSP), located on the DSP/ANI board, contains the TMS320C52 digital signal processor chip
and its required memory. The DSP is responsible for most of the numerical calculations in the ALPS. It performs a recursive
Fourier transform calculation to transform the digitized waveforms into phasor quantities. It also handles the data acquisi-
tion through the ANI section of the board. The keypad, display and communications interfaces are all on the DSP/ANI
Board, as well. Figure 3–9: BLOCK DIAGRAM OF THE DSP / COMM / LUI MODULE is the block diagram of the DSP/ANI
Board.
Figure 3–9: BLOCK DIAGRAM OF THE DSP / COMM / LUI MODULE
ANI CIRCUITRY
MUX
A/D &
LATCHES
TMS320C52
DIGITAL SIGNAL
PROCESSOR
EPROM
PROGRAM
RAM
DATA
DUAL-PORT
RAM
ADDRESS
DATA
CONTROL
CONTROL
LOGIC
TIMER /
COUNTER
SERIAL EPROM
INTERFACE
DIGITAL I/O
INTERFACE
KEYBOARD
INTERFACE
DISPLAY / LED
INTERFACE
FRONT RS-232C
INTERFACE
REAR COMM
INTERFACE PL2
CONTROL
LOGIC
ANALOG
SEQUENCER
CONTROL LOGIC
REAR COMM
INTERFACE PL3
CURRENTS / VOLTAGES
VREF
SYNC
SCAN
ENABLE
END OF
CONVERSION
CLOCK
SEEP LINK
Содержание ALPS
Страница 2: ......
Страница 4: ......
Страница 182: ...5 20 ALPS Advanced Line Protection System GE Power Management 5 5 MOB TESTING 5 FUNCTIONAL TESTS FACTORY SETTINGS 5 ...
Страница 200: ...6 18 ALPS Advanced Line Protection System GE Power Management 6 5 ZONE REACH TESTS 6 FUNCTIONAL TESTS USER SETTINGS 6 ...
Страница 346: ...D 4 ALPS Advanced Line Protection System GE Power Management D 1 KEYPAD MENUS APPENDIXD D ...
Страница 352: ...F 2 ALPS Advanced Line Protection System GE Power Management F 1 WARRANTY INFORMATION APPENDIXF F ...
Страница 366: ...xiv ALPS Advanced Line Protection System GE Power Management INDEX INDEX ...