- 102 -
Screws
(For Comp. Wire)
Pressure Switch Connector
Screws (DB)
Screws (IGBT)
Screws (FRD)
Screws (IPM)
Total 8 speacers
Communication Connector
CT Connector
Screws ( Filter PCB - Inverter PCB Wire
Inverter PCB removal
Remove the 10 mounting screws
(IPM 2, IGBT 4, DB 2, FRD 2)
For screws of IPM.
Note the tightening torque at the installation.
• Temporary tightening : 0.2 to 0.4 N.m
• Final tightening : 0.98 to 1.47 N.m
For screws of IGBT, DB, FRD.
Note the tightening torque at the installation.
• Temporary tightening : 0.1 to 0.3 N.m
• Final tightening : 0.58 to 0.98 N.m
For screws of Comp.
Note the tightening torque at the installation.
• Tightening torque is as follows.
• Final tightening : 1.4 to 1.6 N.m
For screws of Filter PCB - Inverter PCB Wire.
Note the tightening torque at the installation.
• Tightening torque is as follows.
• Final tightening : 2.3 to 2.7 N.m
Remove the 4 connectors (Power supply, CT,
Communication and Pressure switch)
Remove the spacers (8 places)
Spread the heat transfer compound on IPM when
you exchange INVERTER PCB by the repair.
Note at the installation.
1. Remove the old heat transfer compound as possible
from IPM and Diode Bridges when you exchange
INVERTER PCB by the repair.
2. Spread the heat transfer compound evenly on IPM
and Diode Bridges.
3. Prevent foreign matter from attaching to the surface
of IPM and Diode Bridges.
Specifi cations for the heat transfer compound
Manufacturer
Shin-Etsu Chemical Co.,Ltd
Grade
G746
Waterstage / Maintenance Manual / 2105 - EN