- 14 -
Clear 7: Discharge thermistor error
Hydraulic Unit LED:
Green 7 fl ashes / Red 1 fl ash
Outdoor Unit LED:
2 fl ashes
Probable causes:
• Misconnection.
• Sensor failure.
• Main PCB failure.
Check:
1. Check the sensor connection:
-
See if the connector has been disconnected.
-
See if the connection is correct.
-
Check for any damage on the sensor cable.
After solving the misconnection problem, switch the heat pump back on.
2. Remove the sensor and check its resistance value:
- Check the resistance value
Temperature
(°C) 0 5 10 15 20 30 40 50
Resistance (k
) 168
130
101
79 63 40
26,3 17,8
Temperature
(°C) 60 70 80 90 100 120
Resistance (k
) 12,3 8,7 6,3 4,6 3,4 2
- If the thermistor is faulty, replace it.
OK
3. Check the electronic board voltage:
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
- If there is no voltage, replace Main PCB.
OK
THERMISTOR
(COMPRESSOR)
THERMISTOR
(OUTDOOR)
THERMISTOR
(PIPE)
THERMISTOR
(DISCHARGE)
THERMISTOR
(HEAT SINK)
THERMISTOR
(PIPE MID)
THERMISTOR
(EXPANSION)
Waterstage / Maintenance Manual / 2105 - EN