- 48 -
Control Settings
►
General
The settings described below are those which can be
modifi ed by the user.
We wish to remind you that changing the settings below
may cause the heat pump to behave in an undesirable
way. A testing period should be conducted before the
permanent settings of the heat pump are confi rmed.
This may require a number of changes to be made by
the installer.
There are 4 access levels:
U
--> End-user level.
I
--> Commissioning level (installer start-up).
S
--> Engineer level (specialist).
C
--> OEM level (manufacturer) (not available).
▼ Setting parameters
- Selecting the desired level.
- Scroll the list of menus.
- Selecting the desired menu.
- Scroll the function lines.
- Selecting the desired line.
- Adjusting the parameter.
- Validate the setting by pressing
OK
.
- To return to the menu, press
ESC
.
If no setting is made for 8 minutes, the screen
automatically returns to the basic display.
OK
Press and release
End user
OK
OK
OK
Time of day and date
Hours / minutes
1
Time
1...24 h
User interface
Day/Month
2
Minutes
0...60 min
Heating circuit 1 timer
programme
Year
3
...
Press for 3
seconds
End user
Start-up
Specialist
OEM
Time of day and date
Hours / minutes
1
User interface
Day/Month
2
Heating circuit 1 timer
programme
Year
3
...
End date of summer time
4
01.01...31.12
End date of summer time
5
▼ Recommended settings for the parameters depending on the installation's emitters
Very Low Temperature
Radiators /
Heating-cooling fl oor
Low temperature
radiators
Dynamic radiators or
fan-coil heaters
Classic
temperature
radiators
Heating curve
slope
720
(CC1)
1020
(CC2)
0.25 to 0.5
0.5 to 1.25
0.4 to 1.1
1.25 to 3
Curve
displacement
721
(CC1)
1021
(CC2)
0
0
4 *
0
Min.
outgoing value
740
(CC1)
1040
(CC2)
Factory (17 °C)
Factory (17 °C)
30 or 35 °C
Factory
(17 °C)
Max.
initial setpoint
741
(CC1)
1041
(CC2)
50 °C
Factory (55 °C)
65 °C
65 °C
DHW charging
time limitation
5030
Factory (90 min)
Factory (90 min)
40 min
Factory
(90 min)
Waterstage / Maintenance Manual / 2105 - EN