• Calculation of integral
If a fl ow temperature sensor (BX1) is connected and the
heating curve is set to the fl ow temperature setpoint,
the controller uses the fl ow temperature and the fl ow
temperature setpoint for computing the integrals In the
following situations, the integral is set to "0":
- No valid temperature request delivered.
- Setpoint change >2 K.
- Frost protection for the heat pump is active.
- The heat pump has gone to lockout or cannot deliver
any heat for a longer period of time.
- The heat pump is in active cooling mode.
- A buff er storage tank is being charged.
- The function is deactivated.
With active DHW charging, the integral value is frozen.
Max setpoint HP DHW charge
The heat pump setpoint is limited to the parameterized
value during warm water charging. The function can be
switched off . If the fl ow temperature is higher than the
parameterized value, the DHW charging with heat pump
will be stopped and fi nished with electrical immersion
heater or auxiliary heat generator.
With electrical utility lock
This setting relates to input EX1 (load-shedding or
peak day clearing) and allows the electric heaters to be
locked as follows:
• Locked
The heat pump and all electric heaters are locked, both
heat pump stages and the DHW tank electric auxiliary.
Only the boiler backup, if installed, continues to operate
• Released
The heat pump operates and all electric heaters are
locked, both heat pump stages and the DHW tank
electric auxiliary.
The boiler backup, if installed, continues to operate.