- 58 -
Line
Function
Setting range
or display
Setting
increment
Basic
setting
Additional generator (Boiler connection)
3692
S
With DHW charging
Locked, Substitute,
Complement, Instantly
Substitute
- DHW Instantly :
When DHW request, the HP and the boiler are put into operation. The HP will stop when the primary
return temperature is over 55 °C.
- DHW Substitute :
If the outdoor temperature is above 2 °C, the operation of the HP when DHW request last 5 minutes
at least. The HP operating time can be extended depending on the outdoor temperature. The boiler will activate then.
3700
S
Release below outdoor temperature
-50... 50 °C
1 °C
2 °C
3701
S
Release above outdoor temperature
-50... 50 °C
1 °C
--
3705
S
Overrun time
0... 120 min
1 min
20 min
3720
S
Switching integral (for boiler relief)
0... 500 °Cmin
1 °Cmin
100 °Cmin
3723
S
Locking time
1... 120 min
1 min
30 min
Domestic hot water (DHW)
5024
S
Switching diff
0... 20 °C
1 °C
7 °C
5030
S
Charging time limitation
10... 600 min
10 min
90 min
(with dynamic radiator, adjust 40 min)
5055
S
Recooling temp
10... 95 °C
1 °C
65 °C
5057
S
Recooling collector
Off , Summer, Always
Summer
5061
S
Electric immersion heater release
24h / day, Release of DHW,
Programme 4 / DHW
Release of
DHW
5093
S
With solar integration
No, Yes
Yes
Installation con
fi
guration
5700
I
Pre-setting
1, 2, 3,... 9
1
1
This control enables you to choose one of the 4 pre-selected installation confi gurations. The hydraulic layouts for the
various confi gurations are detailed in the section: "Installation Confi gurations".
- Pre-setting 1: 1 heating circuit with or without electrical back-up, with DHW tank.
- Pre-setting 2: 2 heating circuits with or without electrical back-up, with DHW tank.
- Pre-setting 3: Boiler connection and 1 heating circuit and DHW tank.
- Pre-setting 4: Boiler connection and 2 heating circuits and DHW tank.
- Pre-setting 5 and more: Not used.
5710
S
Heating circuit 1
Off , On
On
5711
S
Cooling circuit 1
Off , 4-pipe system cooling,
2-pipe system cooling
O
ff
Set the parameter to
"2-pipe system cooling"
with the cooling kit.
5715
S
Heating circuit 2
Off , On
On
5716
S
Cooling circuit 2
Off , 4-pipe system cooling,
2-pipe system cooling
O
ff
Set the parameter to
"2-pipe system cooling"
with the cooling kit.
If the installation consists of 2 heating circuits.
5731
S
DHW controlling element Q3
No charging request,
Charging pump, Diverting valve
Diverting
valve
5740
S
Output el imm heater K6
0.1... 99 kW
2
5740 = Value of the DHW electrical backup - kW
5806
I
Type el imm heater fl ow
1 : 3-stage, 2 : 2-stage excluding,
3 : 2-stage complementary,
4 : Modulating UX
3 :
2-stage
complementary
5811
S
Output el imm heater K25
0.1-...99
3
Without electrical backup = 0 ; Single phase electrical backup (Factory setting) = 3 ; 3-phase electrical backup = 9
Waterstage / Maintenance Manual / 2105 - EN