- 57 -
Line
Function
Setting range
or display
Setting
increment
Basic
setting
3156 --> 3158 : Not used
3159
U
Energy brought in heating 6 (N - 6)
Kwh
--
3160
U
Energy brought in DHW 6
Kwh
--
3161
U
Energy brought in cooling 6
Kwh
--
3163 --> 3165 : Not used
3166
U
Energy brought in heating 7 (N - 7)
Kwh
--
3167
U
Energy brought in DHW 7
Kwh
--
3168
U
Energy brought in cooling 7
--
3170 --> 3172 : Not used
3173
U
Energy brought in heating 8 (N - 8)
Kwh
--
3174
U
Energy brought in DHW 8
Kwh
--
3175
U
Energy brought in cooling 8
Kwh
--
3177 --> 3179 : Not used
3180
U
Energy brought in heating 9 (N - 9)
Kwh
--
3181
U
Energy brought in DHW 9
Kwh
--
3182
U
Energy brought in cooling 9
Kwh
--
3184 --> 3186 : Not used
3187
U
Energy brought in heating 10 (N - 10)
Kwh
--
3188
U
Energy brought in DHW 10
Kwh
--
3189
U
Energy brought in cooling 10
Kwh
--
3190
S
Reset fi xed day storage
No, Yes
No
Reset the historical counters (1 to 10). The general counter (parameter 3113) is not reset.
3197
S
Compressor electrical power
0.1...60
0.1
See table
below
Set the parameter 3197 according to the outdoor unit
Heat Pump
Outdoor unit
Parameter 3197
excellia (duo) 11 3-phase
WOYK112LCT(A)
4.28
excellia (duo) 14 3-phase
WOYK140LCT(A)
5.13
excellia (duo) 16 3-phase
WOYK160LCT(A)
5.40
3264 --> 3267 : Not used
Note: "Energy" Counters increment as of 1 July each year.
Waterstage / Maintenance Manual / 2105 - EN