Clear 20: Inverter error
Hydraulic Unit LED:
Green 6 fl ashes / Red 3 fl ashes
Outdoor Unit LED:
18 fl ashes
Probable causes:
• Connection failure.
• Main PCB failure.
Check:
1. Check connections in control unit:
- Check if the terminal connection is loose.
- Check if connector is removed.
- Check if connector is erroneous connection.
- Check if cable is open.
Upon correcting the removed connector or mis-wiring, reset
the power.
2. Replace Main PCB :
If Check Point 1 does not improve the symptom, replace
Main PCB.
OK