- 8 -
▼ Outdoor Unit Fault
When the system is switched back on after a power
outage, the Hydraulic Unit may display fault 370 for
a few tens of seconds. This is not a serious problem.
It simply means that the outdoor unit is running its
tests. Once the tests have been completed, the fault
should disappear. If it doesn't, if a fault has occurred
on the outdoor unit as indicated by the Hydraulic Unit,
you must remove the front (right-hand) facing from
the outdoor unit. Faults are coded by LED fl ashes.
Error messages are listed in the table below:
On the outdoor unit
When an error occurs:
- The diode “
ERROR
” (2) blinks.
- Press once on the switch “
ENTER
” (SW109).
- The “
ERROR
” (2) diode blinks several times depending
on the error’s type.
fi
g. 3 - Location of switches and LED on single phase and
3-phases outdoor unit
Waterstage / Maintenance Manual / 2105 - EN