- 39 -
Check point 2 : check winding resistance
Check winding resistance on each terminal
If the resistance value is 0
or infinite, replace compressor.
Check point 3 : replace Main PCB
If check point 1 and 2 do not improve the symptom, replace Main PCB.
Resistance value :
- 0.24
(at 20°C) for single phase type
- 0.79
(at 20°C) for 3-phase type
▼ Service parts information 3 : Outdoor unit electronic expansion valve (EEV, EEV (INJ))
Check point 1 : Check connection
Check connection of connector
(Loose connector or open cable)
Check point 2 : Check coil of EEV
Remove connector, check each winding resistance of
coil.
Read wire
Resistance value
White-Red
Yellow-Red
Orange-Red
Blue-Red
46
+/- 4
at 20°C
If resistance value is abnormal, replace EEV.
Check point 3 : Check voltage from main PCB
Remove connector and check voltage (DC12V)
If it does not appear, replace Main PCB.
Check point 4 : Check noise at start up
Turn on power and check operation noise.
If an abnormal noise does not show, replace Main
PCB.
EXPANSION VALVE
COIL
EXPANSION
VALVE COIL
(INJ)
EXPANSION VALVE COIL
EXPANSION VALVE
COIL (INJ)
Single phase :
3-phase :
Waterstage / Maintenance Manual / 2105 - EN