- 79 -
DHW mode
Holiday
status
Release
(settings 1620)
Time pgm status
(Pgm 4)
Low tari
ff
status
(Ex2)
DHW mode level
Off
x
x
x
x
Frost protection
On
Yes
x
x
x
Frost protection
On
No
…
…
x
…
On
No
Low tariff (OPK)
x
Inactive
Reduced
On
No
Low tariff (OPK)
x
Active
Nominal
On
No
Time pgm 4 or OPK
Nominal
Inactive
Nominal
On
No
Time pgm 4 or OPK
Reduced
Inactive
Reduced
On
No
Time pgm 4 or OPK
Nominal
Active
Nominal
On
No
Time pgm 4 or OPK
Reduced
Active
Nominal
x = indiff erent
Information
Release by low tariff input always triggers forced DHW
charging
If the low tariff input EX2 has not been confi gured and
release via OPK has nevertheless been set, the DHW
level will either continuously remain on reduced or will
follow time program 4.
Legionella Function
Line Nr
Programming line
1640
Legionella function
1641
Legionella function periodically
1642
Legionella function weekday
Legionella function
• Periodically
The legionella function occurs repeatedly according to
the adjusted periodicity (command line 1641).
• Fixed weekday
The legionella function can be activated on a fi xed day
of the week (command line 1642). With this setting,
heating up to the legionella setpoint occurs on the
scheduled day of the week, regardless of the storage
tank temperatures during the previous period.
▼ Swimming Pool Functions
Line Nr
Programming line
2056
Setpoint source heating
The controller enables a swimming pool to be heated
by the heat pump. An individual setpoint can be set by
means of parameter 2056, which appears when the
swimming pool function is activated by parameter 6046
being set to "Swimming pool release".
Use of input H33 requires an extension to be connected
to the control.
Waterstage / Maintenance Manual / 2105 - EN