- 17 -
Clear 10: Heat Sink Thermistor error
Hydraulic Unit LED:
Green 7 fl ashes / Red 7 fl ashes
Outdoor Unit LED:
9 fl ashes
Probable causes:
• Misconnection.
• Sensor failure.
• Main PCB failure.
Check:
1. Check the sensor connection :
-
See if the connector has been disconnected.
-
See if the connection is correct.
-
Check for any damage on the sensor cable.
After solving the misconnection problem, switch the heat pump back on.
2. Remove the sensor and check its resistance value :
- Check the resistance value.
Temperature (°C)
0
5
10
15
20
30
40
50
Resistance (k
) 15,8
12,2
9,5 7,5 5,9
3,78 2,50 1,69
Temperature (°C)
60
70
80
90 100 120
Resistance (k
) 1,17
0,83
0,6 0,44 0,33 0,19
- If the thermistor is faulty, replace it.
OK
3. Check the electronic board voltage:
- Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor (DC5.0V)
- If there is no voltage, replace Main PCB.
OK
THERMISTOR
(COMPRESSOR)
THERMISTOR
(OUTDOOR)
THERMISTOR
(PIPE)
THERMISTOR
(DISCHARGE)
THERMISTOR
(HEAT SINK)
THERMISTOR
(PIPE MID)
THERMISTOR
(EXPANSION)
Waterstage / Maintenance Manual / 2105 - EN