- 116 -
▼ Precautions for exchange of refrigerant-cycle-parts
(1) During exchange the following parts shall be protected by wet rag and not make the allowable temperature or
more.
(2) Remove the heat insulation when there is the heat insulation near the welding place.
Move and cool it when its detaching is diffi cult.
(3) Cool the parts when there are parts where heat might be transmitted besides the replacement part.
(4) Interrupt the fl ame with the fi re-retardant board when the fl ame seems to hit the following parts directly.
(5) Do not allow moisture or debris to get inside refrigerant pipes during work.
(6) When brazing, be sure to replace the air in the pipe with nitrogen gas to prevent forming oxidization scale.
(7) Open the 3WAY VALVE because there is a possibility of squirting the refrigerant from the heated pipes at brazing.
Part name
Allowable
temperature
Precautions in work
SOLENOID VALVE
120°C
Remove the coil before brazing.
And install the coil after brazing.
EXPANSION VALVE
120°C
Remove the coil before brazing.
And install the coil after brazing.
4-WAY VALVE
120°C
Remove the coil before brazing.
And install the coil after brazing.
3-WAY VALVE (GAS)
100°C
3-WAY VALVE (LIQUID)
100°C
UNION JOINT
100°C
Remove the pressure sensor before brazing.
And install the pressure sensor after brazing.
PRESSURE SENSOR
100°C
Tighten the fl are part gripping it. (Tightening torque :15 1.5N m)
Do the static electricity measures.
PRESSURE SWITCH
100°C
Remove the wiring before brazing.
And connect the wire after brazing.
Waterstage / Maintenance Manual / 2105 - EN