Construction
• Mounting method:
Mounted in panel (vertical panel)
Tilt angle
α
= 90 to 60
°
∠ α
• Material:
Case: steel plate
Front flap frame: glass-containing polycarbonate
• Mass:
Approximately 6kg (without options)
Approximately 7kg (with all options)
• External dimensions:
288 x 288 x 199mm
• Painted color:
Case black: front flap frame black
• External terminals:
Screw terminals (M4 thread)
Power supply section
• Rated power voltage:
100 to 240VAC (Free power supply)
• Range of operating power voltage:
85 to 300VAC
• Supply frequency:
50/60Hz both employable
• Power consumption:
100V AC without options approximately 22VA
100V AC with all options approximately 37VA
Conditions for normal operation (for continuous operation of devices)
• Ambient temperature:
0 to 50
°
C
• Ambient humidity:
20 to 80% RH, but temperature
×
humidity < 3200
• Vibration:
10 to 60Hz, 0.2m/s
2
{0.02 G} or less
• Mounting attitude:
Forward tilt 0
°
, rearward tilt within 30
°
, left/right 0
°
• Signal source resistance: Thermocouple input ........ Less than 1k
Ω
Voltage input ................... Less than 0.1% of input resistance
Resistance bulb input ...... Less than 10
Ω
/wire (Resistance of each wire
of 3-wire system should be balanced.)
• Warm-up time:
30 minutes or more
• Impact:
None
Effects of operating conditions:
• With 85 to 300V AC fluctuation (frequency 50 or 60Hz), 100V AC base
Indication variation ................
±
(0.1% of reference range + 1 digit)
Recording variation ................
±
0.2% of record span
• With 47 to 63Hz fluctuation (power supply voltage: 100V AC), 50Hz base
Indication variation ................
±
(0.1% of reference range + 1 digit)
Recording variation ................
±
0.2% of record span