7 - 2
INP-TN4PHAV-E
(1)
Values of parameters at the time of shipment (initial values)
Parameter name
Pass code
Main chart speed
Sub-chart speed
(option)
Alarms
Recording mode
Record range
Input selection
TAG No.
Message print
List print-out
Daily report
Totalize
RS-485 transmission
(option), T-link
transmission
(option)
Time setting
Ink monitor clear
Recording paper
illumination lamp
(option)
State at time of
shipment (initial values)
(Cancelled)
25mm/h
25mm/h
No. 1 to 4: NO
Set value: 0
ALM: 0
Trend recording
Periodic print-out: ON
Scale print-out: ON
Recording format:
Standard
Thermocouple system:
0 to 1200
°
C, K
Resistance bulb system:
0 to 500
°
C, Pt
DC voltage system:
DC -5 to 5V
Thermocouple: K
thermocouples,
°
C
Resistance bulb:
Pt 100,
°
C
DC voltage: V
Input filter: 3 seconds
Scaling: OFF
Rooter: OFF
Logarithmic
calculation: OFF
Subtract calculation: OFF
Blank
Blank
Print position: 0mm
Print timing: Manual
—
Function: OFF
Automatic print-out: ON
Start time: 00:00
End time: 00:00
Function: OFF
Automatic print-out: ON
Start time: 00:00
End time: 00:00
Station No.: 1
Baud rate: 19200 bps
Stop bit: 1
Parity: odd
Current time setting
NO
ON
Remarks
Setting range: 0 to 9999
Setting range: 5 to 1500mm/h
Setting range: 5 to 1500mm/h
Changed by external contact input
4 kinds and 4 points, L, H, RH and RL, are
available for each channel (relay output:
option).
Trend recording/logging recording selection
Periodic digital print-out on/off selection
Fixed interval scale lines, digits, units print-out
selection of ON/OFF
Standard, auto-range recording, zoom records,
zone recording selection
Specification of record range
Input type specification,
°
C,
°
F specification
mV, V' specification
Setting range: 0 to 900 seconds
DC voltage input scaling can be set (working
values, units)
DC voltage input rooter (square root extractor)
can be specified
Recording of differences between channels can
be specified
Up to 8 alphanumeric characters
10-message, alphanumeric: Within 16
characters
Parameter list print-out, scale print-out, test
pattern print-out, daily report, totaling list
Daily report function on/off selection, start
time selection
Daily report list automatic print-out on/off
selection
Daily report operation on/off setting for each
channel
Totalize function on/off selection, start time
selection
Totalize list automatic print-out on/off selection
Totalize operation on/off setting for each channel
Specified if there is connection with parent
CPU
Display in the order, Yea, Month, Day, Hours,
Minutes
Setting of ink end warning-detection function
Always set to clear (YES) after recording head
replacement
Set to "OFF" to turn out the recording paper
illumination lamp
Method of setting
checking
Section 7.3
Section 7.4
Section 7.4
Section 7.5
Section 7.6
Section 7.7
Section 7.8
Section 7.9
Section 7.10
Section 7.11
Section 7.12
Section 7.13
Section 7.14
Section 7.16
Section 7.16
Section 7.17
Skip/copy
setting