7 - 14
INP-TN4PHAV-E
(1)
Setting and changing input signal type
DC voltage
Thermocouple
Resistance bulb
To effect the changes refer to Section 5.3 to change the positions of the setting pins.
Then, use the following parameter specification to specify the correct input signal type.
Example: Changing 5V input signal type of channel 6 to thermocouple input
Use the
,
keys to select channel 6 and press the ENT key.
The current '5V' value is flashing: press the
,
keys to select
the 'K' input type and press the ENT key.
Note:
The type of input is displayed in the following order by pressing the
key (in reverse order
with
key).
K
E
J
T
R
S
B
N
W
L
U
PN
Pt
JPt
50mV
500mV
COM
50V
5V
Copy
Skip
There is output of a display asking you to check the change in
setting pins and the type of input after the change. Please check
that the work of changing the setting pins has been completed.
If everything is OK, press the ENT key.
(2)
Setting and changing the input filter
If there is no change in the filter, press the ENT key.
Input filter setting range: 0 to 900 sec. (in 1 sec. Units)
There is a move to the next parameter.
(3)
Scaling, scaling ranges, units
• For DC voltage input, scaling is set to "ON" or "OFF".
• The
and
keys are used to set the measurement range.
(The left-hand side is the lower limit and the right-hand side the upper limit.)
• The
and
keys are used to specify scaling range for the corresponding measurement range.
(Range of -32767 to 32767; decimal point can be located anywhere)
Ch1
K
°
C
FILTER
T=3sec
Ch1
K
°
C
FILTER
T=3sec
↓
ENT
Ch6
K
°
C
Jumper Setting OK?
↓
ENT
Ch6
K
°
C
FILTER
T=3sec
SUBTRACTON
Ch1
→
Ch0
→
Ch6
↓
ENT